Basic Operation
Buttons (Front Panel)
"POWER" Button
• To turn the UPS ON: with the UPS plugged into a live AC wall outlet*, press
and hold the POWER button for one second.** Release the button. If utility
power is absent, you can "cold-start" the UPS (i.e.: turn it ON and supply power
for a limited time from its batteries***) by pressing and holding the POWER
button for one second.**
• To turn the UPS OFF: with the UPS ON and receiving utility power, press and
hold the POWER button for one second.** Then unplug the UPS from the wall
outlet. The UPS will be completely OFF.
* After you plug the UPS into a live AC outlet, the UPS will automatically charge its batteries, but will
not supply power to its outlets until it is turned ON. ** The alarm will beep once briefly after the indi-
cated interval has passed. *** If fully charged.
"MUTE/TEST" Button
To Silence (or "Mute") UPS Alarms: briefly press and release the MUTE/TEST
button.*
To Run a Self-Test: with your UPS plugged in and turned ON, press and hold
the MUTE/TEST button for two seconds.* Continue holding the button until
the alarm beeps several times and the UPS performs a self test. See "Results of
a Self-Test" below. Note: you can leave connected equipment on during a self-test.
Your UPS, however, will not perform a self-test if you have placed it in
"Standby/Charge-Only" mode (see "POWER" Button description).
CAUTION! Do not unplug your UPS to test its batteries. This will remove
safe electrical grounding and may introduce a damaging surge into your
network connections.
Results of a Self-Test: The test will last approximately 10 seconds as the
UPS switches to battery to test its load capacity and battery charge. All LEDs
will be lit and the UPS alarm will sound.
• If the "OUTPUT LOAD LEVEL" LED remains lit red and the alarm contin-
ues to sound after the test, the UPS's outlets are overloaded. To clear the over-
load, unplug some of your equipment and run the self-test repeatedly
until the "OUTPUT LOAD LEVEL" LED is no longer lit red and the
alarm is no longer sounding.
CAUTION! Any overload that is not corrected by the user immediately
following a self-test may cause the UPS to shut down and cease supplying
output power in the event of a blackout or brownout.
• If the "BATTERY WARNING" LED remains lit and the alarm continues
to sound after the test, the UPS batteries need to be recharged or
replaced. Allow the UPS to recharge continuously for 12 hours, and
repeat the self-test. If the LED remains lit, contact Tripp Lite for service. If
your UPS requires battery replacement, visit www.tripplite.com/
support/battery/index.cfm to locate the specific Tripp Lite replacement
battery for your UPS.
* The alarm will beep once briefly after the indicated interval has passed.
7