Table 11-1 Status indications
String
The drive is inhibited and cannot be run. The Drive Enable signal is not applied to
Inhibit
the drive enable terminal or is set to 0.
The drive is ready to run. The drive enable is active, but the drive inverter is not
Ready
active because the final drive run is not active
Stop
The drive is stopped / holding zero speed.
Supply Loss
Supply loss condition has been detected
dc Injection
The drive is applying dc injection braking
The drive has tripped and no longer controlling the motor. The trip code appears on
Trip
the display.
Under
The drive is in the under voltage state.
Voltage
STEP 12: Understand key parameters and restoring default
When changing a parameter, the new value is saved when pressing the Enter button to return to parameter view
mode from parameter edit mode.
Restoring default parameters:
1.
Ensure the drive is not enabled, i.e. terminal 31 and 34 are open.
2.
Select 'Reset 50 Hz Defs' (50 Hz settings) or 'Reset 60 Hz Defs' (60 Hz settings) in Pr 00.000
3.
Press the red reset button
Parameter
00.001 Minimum Speed
00.002 Maximum Speed
00.003 Acceleration Rate 1
00.004 Deceleration Rate 1
00.005 Drive Configuration
00.006 Motor Rated Current
00.007 Motor Rated Speed
00.008 Motor Rated Voltage
00.009 Motor Rated Power Factor
00.010 User Security Status
Unidrive M400 Step By Step Guide
Issue Number: 2
Description
Range ( )
0.00 to Pr 00.002 Hz
0.00 to 550.00 Hz
0.0 to 32000.0 s/100 Hz
0.0 to 32000.0 s/100 Hz
Refer to the Quick Start Guide for further
information on all drive configurations
0.00 to Drive Rating Amps
0.0 to 33000.0 rpm
0 to 240 V or 0 to 480 V
0.00 to 1.00
Refer to the Quick Start Guide for further
information
Drive output
stage
Disabled
Disabled
Enabled
Enabled
Enabled
Disabled
Disabled
Default ( )
0.00 Hz
Def.50: 50.00 Hz
Def.60: 60.00 Hz
5.0 s/100 Hz
10.0 s/100 Hz
AV
Maximum Heavy Duty
Rating Amps
Def.50: 1500.0 rpm
Def.60: 1800.0 rpm
110V drive: 230 V
200V drive: 230 V
400V drive Def.50: 400 V
400V drive Def.60: 460 V
0.85
Level 1
9