FIXING THE BURNER TO THE BOILER

The burner must be applied to the boiler iron plate after having fixed the supplied stud bolts according to the drill-
ing template. It is advisable to electrically weld the stud bolts inside the plate so as to prevent them from being
extracted jointly with the burner check nuts if the burner is dismantled.
To insert the insulating flange, which must be placed between the burner and the boiler plate, dismantle the end
part of the combustion head. To connect the burner to the boiler, the special nuts and relevant washers are sup-
plied with the burner. The burner is equipped with cylindrical combustion head; it is advisable to first fix the boiler
plate, and then the burner. An insulating protection having a minimum thickness of 0 mm must be placed between
plate and boiler when the boiler port is not provided with thermal insulation.
The boiler plate must be designed according to our drawings, with a minimum thickness of 0 mm. so as to prevent
possible deformations. Before applying the burner to the boiler, the sliding flange must be arranged so as to allow
the burner head to penetrate in the combustion chamber by the amount required by the manufacturer.
Once this operation has been finished, connect the burner to the gas pipes as explained in the following pages,
based on the available type of gas supply (low pressure or mean pressure).
MEASURING THE PRESSURE IN THE COMBUSTION CHAMBER
If the hole in the door is too small to allow the hose to pass and the door has no flame inspection window
it will be necessary to make a Ø 12 hole at the site of the 1/4" connection for the insertion of the pressure
take up hose in the combustion chamber (provided with the burner).
Pressure transmission pipe in
combustion chamber
Pressure take-off in
combustion chamber
Pressure detection pipe connection
nipple in combustion chamber
29 / 76
0006080799_200708
REV.:2002/11/13
Burner flange
N° 0002933641
Plate and refractory
wall hole to be
drilled to Ø 2