to the Main Receiver, Local Port 1 and Alarm Port 1 address have been entered. Furthermore, the Enable supervision
and Supervision time boxes refer only to the main receiver.
APN1 Username and Password, APN2 Username and Password
Some providers may require a user name and password to validate communication. If needed, enter this information here.
APN2 Username and Password are considered to be backup data.
Telephone numbers to decode
This communicator permits to communicates the events in the Contact ID format, via the GPRS network, also to the control
panels that do not support this communication method.
To do this, you must setup a telephone number (the phone numbers can be "virtual" or "real") on the control panel for event
communication in Contact ID format (e.g. you can setup 0123), then you must enter the same telephone number in one of this
fields (you can program up to four telephone numbers for this function).
When the Communicator recognises a call from one of these numbers, automatically transcodes the event in digital format
and forwards it on the GPRS network to the set receiver (refer to the ―Main Receiver‖ and ―Backup Receiver‖ options).
The telephone number must be of at least 2 digits.
The options ―Prefix‖ and ―Digits to Remove‖ have no effect on the ―Telephone numbers to decode‖.
The ―Telephone numbers to decode‖ must exactly match with the telephone numbers set for the control panel.
Leave this fields empty if you don't use this function.
For this feature to work correctly, the "Main Receiver" (and, where necessary the "Backup Receiver") option
must be selected.
DNIS
If required, enter the Dialled Number Identification Service number.
Account code
The account code for communication with SYSTEM III or SYSTEM II receivers must be entered in this box.
Enable Supervision
To enable supervision, select this option. The supervision option is ONLY available to the main receiver. The supervision
messages are not sent when the device is performing a voice call (on GSM).
Supervision time (sec)
Set the Supervision time for the monitored receivers. It is possible to set a Supervision time between a minimum of 5 second
and a maximum of 65535 seconds, with steps of 1 second.
Remote programming (BGSM-120 series only)
This interface makes it possible to use the functionalities of the BGSM-120/BGSM-100 Console software via a network. The transmitter
parameters can be managed remotely using this interface. To use this function, visit the web address http://www.bentelreachme.com.
Enabled: To enable the Remote Programming, click this check box to enter a tick (this setting is enable by default).
Encryption key: The encryption key can be set so that the Remote Programming cannot be accessed by unauthorised persons.
The encryption key may include between 1 and 32 hexadecimal characters. The default setting is 0 (encryption key not enabled).
Status
This page will allow you to monitor and control in real-time all the Communicator functions.
ATTENTION: This page is updated every 5 seconds.
Status section
This section lists the most important data relating to the GSM module. The virtual display shows, in addition to the name of
the GSM network manager, the GSM signal strength (this is displayed through a special indicator).
The Device status indicator may be ON or OFF .The Device status indicator light when it is GREEN: proper function. When
it is RED, this indicates that there is no communication between the software and the device; if it is ORANGE it means that
there is a communication in course. For GPRS Main Receiver and GPRS Backup Receiver this indicator is ORANGE when
the Receiver is initialized but NOT currently connected OR connected but NOT yet initialized.
BGSM-100/120
G
21