A further guarantee of security regarding the signal transmissions from Air2
remote-control keys is provided by the use of a rolling code algorithm. These
random codes allow the Air2-BS200 to authenticate the validity of each
transmission from remote-control keys.
In the event of irregular wireless activity, denial-of-request will be signalled by an
audible error signal ("bop").
To reset wireless transmissions and rolling code authentication, press and hold
keys "F3" and "F4" simultaneously.
This feature is active at default but can be disabled during the programming phase
of the Air2-BS200 module (details follow). If an Air2-KF100 remote-control key is
used on several systems, it is impractical to leave this feature enabled.
The Air2-FD100 detector is capable of sensing the presence of smoke particles
and thus detecting a fire in its early stages.
Air2-FD100 optical smoke detector is equipped with a sampling chamber (based on
light scattering mass - Tyndall effect). In order to ensure the proper operating capacity
of the device, it must be installed away from drafts and large objects which may alter
the airflow to the sampling chamber.
The sole task of the Air2-FD100 smoke detector is to sense for smoke in the
protected area. Therefore, in no way can the combination of a system and an Air2-
FD100 smoke detector be considered a fire control system.
Table 16: Air2-FD100 technical specifications
Battery
"Low battery" fault voltage
Current draw
Operating environmental
conditions
Height (base included)
Diameter (base included)
(base and battery included)
Security rating
Environmental class
The operating parameters can be changed and adapted to the environmental
conditions, either from the control panel or through the SmartLeague software
application. The detector signals alarm status when the level of smoke in the
protected environment reaches the following levels:
•
0.08 dB/m (pre-set mode)
•
0.10 dB/m
•
0.12 dB/m
•
0.15 dB/m
Table 17: Description of Air2-FD100 parts
(Figure 5 - Air2-FD100, a, page 114)
A
Detector
B
LED red/yellow/green
C
Optical chamber
D
Battery
The tricolour LED (360° visibility) indicates the detector status.
•
Green - one flash every 15 seconds: detector not operating properly.
•
Green - one flash every 40 seconds: low battery.
•
Yellow - On solid: fault present.
•
Yellow - flashing: sampling chamber contaminated (with dust, etc.).
•
Red - On solid: detector in alarm status.
Description of products
Air2-FD100 smoke detector
type
estimated life
during standby
maximum
temperature
relative humidity
Weight
E
F
G
H
Lithium CR17450 3V
3 years
Less than 2.4V
70μA
Max 40mA
from -10 to +40°C
93% without condensation
60mm
114mm
182 gr
2
II
Tamper microswitch
ENROLL microswitch
Base
Mounting screw hole
ROLLING-CODE
AUTHENTICATION
2-5
EN 50131-1
EN 50131-5-3
EN 50130-4
EN 50130-5
CEB T031
ATTENTION!