Store Test Results - Fluke 1550C Manual Del Usurario

Ocultar thumbs Ver también para 1550C:
Tabla de contenido

Publicidad

1550C/1555
Users Manual
If breakdown occurs with ramp test enabled, push  before going to
step 4.
Following termination of an insulation test, the Tester beeps when a
potentially hazardous voltage remains on the test terminals due to
charged-circuit capacitance or from the presence of an external voltage.
4. When the test is terminated, STORE RESULT? Is displayed. If
appropriate, store the test results as described in the next procedure.
Otherwise, terminate the STORE RESULT? Prompt by pushing .
The results are not stored.

Store Test Results

Upon completion of an insulation test, the Tester displays STORE RESULT?
As a prompt to save the measurement results for future use. The Tester
includes enough memory to store the results of 99 insulation tests for future
use.
To store the results of an insulation test:
1. Push  to save the measurement results. The Tester will assign and
display a sequential tag number (00 to 99) to identify the measurement.
2. If the tag number is acceptable, push  to store the data. If a different
tagging convention is required, proceed as follows to provide a custom 4-
character tag.
a.
Notice that * is blinking on the display. This is the first of the four
characters available for tagging the test results. Repeatedly push 
to cycle through the character positions.
b. At each character position use  or  to assign a character (0-9,
A-Z).
c.
Push  to store the results.
22

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

1555

Tabla de contenido