Advanced Functions - Comelit Simple Key SK9011 Hoja Técnica

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

again, the reset is complete.
Toggling back to operating mode.
Resetting enables:
- the deletion of one or more building codes.
- the deletion of the transmitter black list.
- the timer to be set to 2 seconds.
- the logical address to be set to 1.
- the password to be set to "0000 ".
Setting the date and time
To work properly the SK9011 unit's internal clock must be set correctly. This is set in
the factory to GMT time (universal time) and will be adjusted automatically to the
corresponding time zone in the place it is being used when it is initialised (first key
swiped).
If necessary, it is, however, possible to set the time and date manually using the
SK9093 software supplied separately. To do this you just have to connect to the unit
using the cable supplied with the kit and launch the program.
- Click on "Clock" and then follow the instructions to change the setting.
- Other functions are possible (changing the password, reinitialising the unit etc.).
Refer to the software instructions.

ADVANCED FUNCTIONS

Event management
The SK9011 unit stores the last 1000 events in its memory (access authorised, access
refused, cancelled transmitter, etc.)
Providing the SK9013 reader unit has been previously networked to the control unit,
events can be recovered using transfer token ref. SK9053 , supplied separately.
After initialising it with the SIMPLEKEY ADVANCED software, place the transfer token
in front of the reader until the green LED stops flashing. Once saved, you just have to
put it in the encoder linked to the micro-computer and follow the software instructions
to transfer the events in the database.
Network Mode
It is possible to network the various system units in order to take advantage of the
following functions from the management micro-computer:
• Modifying unit parameters
• Setting the date and time
• Retrieving events automatically or on command
• Remote opening command
• Immediate deletion of a lost transmitter
It is possible to network up to 255 units in one system. 3 types of network are possible:
• An RS485 wired network using a USB converter ref. 48756 (one per system) - a
maximum of 32 units
It is vital to record on the unit the same logical address as the one recorded in
the software. To do this use the S3 push button giving the pulse number
corresponding to the address. (between 1 and 32) then validate it by holding the
S1 push button down for 5 seconds.
• A TCP/IP Ethernet network by adding the SK9072 converter to each unit - a
maximum of 254 units
Keep the default value of the logical unit address
• Mixed network: Ethernet TCP/IP over several branches (with the SK9072
converter) then the RS485 wired cabling on each branch - a maximum of 32
units per branch, 255 units in total
The units must be addressed from 1 - 32 on each branch.
For detailed use of the functions please refer to the SIMPLEKEY ADVANCED software
instructions
Technical characteristics
• Capacity: 30 building codes
• Opening time can be adjusted from between 1 and 99 seconds.
• Output via dry contact max. 5A at 250 VAC
• Power consumption: 35 mA when idle, 100 mA when relay active
• Operating temperature: -10°c - +55°c
• Operating voltage: 12 Vdc
• Dimensions (H X L X D): 55 x 85 x 20 mm
• Coverage 50 metres in a free field (indicative)
Optional extra: offset aerial SK9014
This may be used to improve the range of the receivers and may have to be used when
the receiver is put in a metal casing or is close to large amounts of metal.
FT SK9011
5
FT SK9011