Programming; Level One Programming (On-Off Functions) - Nice Moon MC824HR Instrucciones Y Advertencias Para La Instalación Y El Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 33
6 Before commissioning the automation, ensure that the owner is adequately
informed of all associated risks and hazards.
For all the above-mentioned documentation, Nice provides instruction
manuals, guides and pre-filled forms through its technical support service.
Also see: www.nice-service.com
5

PROGRAMMING

The control unit has 3 keys OPEN ( ), STOP (SET), CLOSE ( ) that can be
used both for controlling the unit during testing and for programming the avail-
able functions.
The programmable functions available are divided into 2 levels and their relative
operating status is displayed by means of the 8 LEDs (L1...L8) on the control
unit (LED lit = function active; LED off = function not active).
Use the programming keys:
OPEN ( ): – key for controlling gate opening; – selection key during programming.
STOP/SET: key for stopping a manoeuvre; if pressed for more than 5 sec-
onds, it enables entry to programming mode.
CLOSE ( ): – key for controlling gate closure; – selection key during programming.
LED Function
L1
Automatic closure
L2
Reclose after photo
L3
Always close (*)
L4
Stand by (Bluebus)
L5
Electric lock/Courtesy light
L6
Pre-flash
L7
"Close" becomes "Partial open 1"
L8
Automatic 1
(*) Function active by default
01. Press and hold down the "Set" key for approx. 3 seconds;
02. Release the key when LED "L1" starts flashing;
03. Press the " " or " " key to move the flashing LED to the LED representing the function to be modified;
04. Press "Set" to change the status of the function:
(short flash = OFF; long flash = ON);
05. Wait 10 seconds (maximum time) to exit the programming mode.
Note – During this procedure, points 03 and 04 need to be repeated when programming other functions to "ON" or "OFF" during the phase itself.
TABLE 4 - First level functions
Description
Function ACTIVE: after an opening movement, there is a pause (equal to the programmed time) after
which the control unit automatic initiates a closure movement. The factory setting for the Pause time is
30 sec.
Function NOT ACTIVE: function is "semiautomatic" type.
Function ACTIVE: if the photocells are activated during the opening or closing manoeuvre, the pause time
is reduced to 5 seconds regardless of the programmed pause time.
With "automatic closure" disabled, if the photocells are activated during closure the "automatic closure" is
activated with the programmed "pause time".
Function ACTIVE: in the event of a power failure, even of short duration, when power is restored the
control unit detects gate open and automatically starts a closure manoeuvre, preceded by 5 seconds of
pre-flashing.
Function NOT ACTIVE: when power is restored the gate remains where it is.
Function ACTIVE: 1 minute after the end of the manoeuvre, the control unit turns off the "Bluebus" output
(connected devices) and all the LEDs apart from the Bluebus LED which will flash more slowly. When the
control unit receives a command normal operation is restored (with a short delay). This function has the
purpose of reducing consumption, an important aspect with battery or photovoltaic panel power supply.
Function ACTIVE: the "electric lock" output switches its operation to "courtesy light".
Function NOT ACTIVE: the output operates as an electric lock.
Function ACTIVE: a 3 second pause can be added between the flashing light signal and the start of the
manoeuvre to provide advance warning of a hazard situation.
Function NOT ACTIVE: flashing light signal coincides with the start of the manoeuvre.
Function ACTIVE: the "Close" input of the control unit switches operation mode to "Partial Open 1"
ACTIVE Function: with the gate open and with "automatic closing active", the commands coming from the
inputs and the Radio receiver are disabled during the pause time. The operation of these commands is
restored when the pause time elapses, immediately after the closing manoeuvre has begun.
NOT ACTIVE Function: the commands also work during the pause time.
TABLE 5 – Programming procedure (first level functions)

5.1 - Level one programming (ON-OFF functions)

All the first level functions can be programmed by default on "OFF" except for
the always close function which is "ON". The functions may be changed at
any time. To check the various functions see Table 4. For the programming
procedure see Table 5.
IMPORTANT – In the programming procedure, the maximum time interval
that can elapse between activation of one key and the next is 10 seconds.
When this time elapses, the procedure terminates automatically, memorising
the modifications made up until then.
SET
3 s
SET
L1
or
SET
10 s
English – 5

Publicidad

Tabla de contenido
loading

Tabla de contenido