Installation Instructions; Battery Installation; Selecting A Location - Johnson Controls tyco WS4933 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Instructions

Battery Installation

To replace the battery:
1. Remove the detector from its mounting base by twisting it counterclockwise.
Remove and dispose of the battery according to your local regulations.
2. To ensure proper power-down sequence, wait a minimum of 20 seconds before
installing the new battery.
3. Install a new, 3-volt CR123A Panasonic lithium battery in the battery com-
partment observing the correct polarity. If the battery is incorrectly inserted,
remove gently with a flathead screwdriver and correctly reinsert.
4. Reinstall the detector onto the mounting bracket by turning it clockwise.
5. After the power-up sequence, the green LED blinks once every 12 seconds to
indicate normal operation. If the battery is not installed correctly, the detector
will not operate and the battery may be damaged.
Enrollment
At the alarm control panel, program the 6-digit serial number of the WS4933 (located
on the back of the detector). Please refer to your control panel installation manual for
details.

Selecting a Location

Selecting a suitable location is critical for the CO detector. The Consumer Product
Safety Commission (CPSC) recommends to use at least one CO detector per house-
hold, located as near as possible to sleeping areas of the home, because the human
body is most vulnerable to the effects of CO gas during sleeping hours.
Figure 2: CO Detector Placement
Legend
A: Bedroom
B: Living Room
C: Kitchen
D: Basement
E: Garage
For added protection, install additional CO detectors in every bedroom and on every
level of your home. If your bedroom hallway is longer than 14 meters (40 feet), install
a CO detector at BOTH ends of the hallway. Install an additional detector 6 meters
(20 feet) away from the furnace or fuel burning heat source. For maximum protection,
the detector should also be located outside primary sleeping areas or at each level of
your home. Mount the detector on a firm wall or ceiling.
DO NOT install CO detectors:
In locations where temperature may be below 0ºC (14ºF) or above 40ºC (104ºF).
l
In locations where humidity is below 10% or above 93% RH non-condensing.
l
Near paint thinner fumes.
l
Near air conditioners, furnaces, stoves, fireplaces and any other ventilation source
l
that may interfere with CO gas entering the detector.
In locations where furniture or draperies may obstruct the air flow.
l
In exhaust streams from gas engines, vents, flues or chimneys.
l
Where dirt or dust could collect and block the sensor and prevent it from working.
l
In locations that can be reached by children.
l
In turbulent air from ceiling fans.
l
In close proximity to an automobile exhaust pipe - this will damage the detector.
l
Mounting
The detector can be mounted on a wall or ceiling. For EN approved sites, only ceiling
installation is allowed.
The CO detector must be mounted with its bracket (when it is attached to its bracket
the tamper switch is pressed and the detector automatic reset is performed).
1. Refer to Figure 3 and install using screw locations as required. Maneuver the
mounting bracket so the screws are at the elbow of the screw slots and secure.
2. Fit the detector inside the mounting bracket by aligning it as shown in Figure 3
(detector's alignment notch should be slightly offset from the mounting bracket
tamper release tab), then turn the detector in a clockwise direction until it clicks
into place.
3. Test the detector after completing the installation (as described in the Testing the
Detector section of this manual) and refer to the alarm control panel installation
manual for additional information concerning the use of wireless devices.

Publicidad

Tabla de contenido
loading

Tabla de contenido