1.8.8 Control Supervisor Object, Class 29
Atributos de la Instancia 1
Atributo Acceso
3
Get/Set Run 1
4
Get/Set Run 2
5
Get/Set NetCtrl
6
Get
State
7
Get
Running 1
8
Get
Running 2
9
Get
Ready
10
Get
Fault
12
Get/Set Fault Reset
13
Get
Fault Code
15
Get
Crt From Net
Nombre
Run forward
Run reverse
0 = Local Control
1 = Control from Network
0 = Vendor Specific
1 = Startup
2 = Not ready
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault Stop
7 = Fault
Running forward
Running reverse
0 = Other State
1 = Ready or Enabled or Stopping
0 = No Faults Present
1 = Fault Occured
0 = No Action
0 → 1 = Reset Fault
If fault is active, this atribute
indicates the code for the fault. If
fault is not active, it indicates the
last error code.
0 = Control is local
1 = Control is from Network
Guía DeviceNet Drive Profile MVW-01
hex
Descripción
Padrón
Tipo
BOOL
BOOL
BOOL
UINT8
BOOL
BOOL
BOOL
BOOL
BOOL
UINT16
BOOL
MVW-01 | 27