5.3

Mounting the product

 Verify that the permissible ambient temperature is not exceeded.
 Verify that the product is not mounted the product on top of or next to a
non-insulated boiler part, above opening dampers at furnaces or to the
flue gas pipe.
 Verify that the float housing points vertically to the top.
LEAKING PRODUCT
Verify that you use a screwed pipe connection as per DIN 3852 with cylindri-
cal thread (G thread) and seal the screwed pipe connection with a flat gasket
or with suitable glue. Do nut use Teflon tape or hemp.
Failure to follow these instructions can result in equipment damage.
3. Mount the suction line into the female thread G
cylindrical screwed pipe connection G
torque is 40 ±10 Nm.
Mounting
A
NOTICE
3
/
1. Mount the product to the
boiler casing using the
enclosed bracket and four
self-tapping screws.
2. Use the bracket as a tem-
plate when screwing in the
self-tapping screws. The
arrow (A) must point
upwards.
3
of the housing with a
/
8
as per DIN 3852. The tightening
8
FloCo-Top-1K
EN
14