8. INSTALLER PARAMETER DESCRIPTION
To access to these installer parameters, installer has to go to user parameter number 15.
After, he presses and holds validation key
holding
button
BT-D03-MOI-FR-W-EN-06-19
EN
Accessing to installer parameters
Selecting temperature sensor used for the regulation:
- AIR: regulation with internal sensor
- Amb: regulation with external sensor
- FLR: regulation on floor sensor (external sensor of remote,
only when thermostat is connected to master) or embedded
sensor on receiver
- FLL: regulation with floor sensor and air sensor
Factory setting value: Air
Displaying of measured temperature by internal sensor:
If "Err" is displayed, internal sensor is damaged.
Displaying of measured temperature by external sensor:
➤ FLOOR temperature / AMBIENT temperature
If "Err" is displayed, external/ambient sensor isn't connected
or damaged.
Displaying of measured temperature by floor sensor
connected to receiver (only with specific bidirectional
system)
If "Err" is displayed, thermostat isn't associated to a received
with floor sensor or this sensor is damaged.
Lower limit of floor temperature (FL.L)
This value is used when parameter 20 is FLL
Factory setting value: "no": not activated
Other values: 5°C to "FL.H"
High limitation of floor temperature (FL.H)
This value is used when parameter 20 is set on "floor limit"
FLL.
Factory setting value: "no": not activated
Other values: "FL.Lo" to 40°C
during 5 seconds:
holding
button
Other values: Amb / FLL / FLR
Installer
parameters
releasing
button
15