Rack UPS
MODEL
CAPACITY
INPUT
Nominal Voltage
Voltage Range
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Line
Battery
Transfer
Time
Inverter
EFFICIENCY
AC Mode
ECO Mode
Battery Mode
BATTERY
Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Type
Long-run
Numbers
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H
mm
Standard
Model
Net Weight (kgs)
Dimension, D X W X H
Long-run
mm
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude*
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
*If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
**Product specifications are subject to change without further notice.
10KR
10000VA / 9000W
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
90.5%
86%
12 V / 9 Ah
20(18-20 adjustable)
1.0 A ± 10% (max.)
4.0 A ± 10% (max.)
UPS: 668 x 438 x 266[6U]
Battery pack : 580 x 438 x
133[3U]
UPS:42
Battery pack:63
668 x 438 x 266
42
Less than 60dB @
1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Power management from SNMP manager and web browser
15KR
15000VA / 13500W
3 x 400 VAC (3Ph+N)
190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Three phase with Neutral
≧ 0.99 at 100% Load
Three Phase with Neutral
3 x 400 VAC (3Ph+N)
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1 max
0 ms
91%
96%
87%
12 V / 9 Ah
2 x 20(18-20 adjustable)
9 hours recover to 90% capacity
2.0 A ± 10% (max.)
273 VDC ± 1%
Depending on applications
18 - 20
4.0 A ± 10% (max.)
273 VDC ± 1%
UPS: 668 x 438 x 266[6U]
Battery pack : 580 x 438 x
133[3U] x 2 pcs
UPS:45
Battery pack:63 x 2 pcs
668 x 438 x 266
45
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m
33
20KR
20000VA / 18000W
91.3%
88%
12 V / 9 Ah
2 x 20(18-20 adjustable)
2.0 A ± 10% (max.)
4.0 A ± 10% (max.)
UPS: 668 x 438 x 266[6U]
Battery pack : 580 x 438 x
133[3U] x 2 pcs
UPS:45
Battery pack:63 x 2 pcs
668 x 438 x 266
Less than 65dB @ 1 Meter
45

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

10kl15k15kl20k20kl30k ... Mostrar todo