DINAMIC 1.1
• Check terminal connections and power supply cable cables.
• Connect the wire clamps (these may be in the control panel or control module).
(If the error persists, contact an Authorised Technician).
• Dismount the front and correctly connect the electronics in the keyboard.
• Check and correct the position of the power supply cables to the battery.
• Replace the electronics.
• Connect the wire clamp of the compressor.
• Check the load by checking the pressure, if it is below 0.5 bars or above 5.0 bars with
the equipment operating, recover the load and empty for at least 30 minutes, and then
introduce 300 g in the circuit.
• Clean the condenser with pressurised air.
• Connect or replace the electro.
• Check that the 3 terminals of the electro are connected in the control module.
• Check the pressure and, if it is below 0.5 bars with the equipment operating, clean the circuit
or replace the obstructed components (possibly the continuous flow capillary tube, as this is
the component of least diameter).
• Clean the obstruction of the waste water tube and valve.
• Seal the waste water tube output and the cables located underneath the adapter protector
in the exterior section.
The recovery of the gas will never be exact, since part of the gas remains in the hand
gauge tubes.