3.4.Event ID Descriptions
Event ID
E01
E02
E03
E04
E06
E07
E08
E09
E11
E12
E14
E18
E19
A56
A57
A59
A60
A61
A62
A64
A66
A68
A69
ON-LINE 1000VA / 2000VA / 3000VA
Description of Cause
Bus Start Fail: ​ D C-DC converter or bus sensing circuit
failed.
Bus Volt High:​ DC-DC converter failed.
Bus Volt Low: ​ D C-DC converter failed.
Bus Unbalanced: ​ D C-DC converter failed.
INV Start Fail: ​ I nverter circuit failed.
INV Volt High: Inverter circuit or output voltage
sensing circuit failed.
INV Volt Low: The load may be too heavy or inverter
circuit failed.
INV Short: ​ T he inverter circuit failed.
Bat Volt High: The external battery module connection
is wrong, or the charger failed.
Bat Volt Low: ​ B atteries failed.
Over Load: ​ U PS is overloaded.
Fan Fail: ​ T he ventilation hole has been covered, or the
fans can't work.
Over Temperature: High ambient temperature, or the
ventilation hole has been covered.
Bat Volt Low:​ Battery voltage is low.
Bat Cap Low:​ Battery capacity is low.
Bat disconnect:​ Battery is disconnect.
Overcharge: ​ C harger voltage is high.
Charger fail:​ Charger is failed.
Bat Bad:​ Battery failed.
Over Load warning: ​ U PS is overload.
EPO Off:​ Missing the EPO connection
High Temperature: High ambient temperature, or the
ventilation hole has been covered. This is shown only
when start up UPS.
Fan Lock: ​ f ans can't work because of lock.