1. Model Installation
■ You are required to prepare the ceiling suspension bolts, nuts and washers.
■ Install the unit firmly and horizontally enough to support its weight. (Fig. 1)
■ If you do not fit it firmly, it is not only dangerous but also easily vibrated. If it is
not fitted horizontally, the damper unit becomes defective in operation.
Caution
• When you are required to be cautious on prevention of vibration, we
recommend you to use the anti-vibration ceiling suspension fixtures.
• Never fail to make an inspection opening with
shown on the paragraph of "Cautions For Operation", so that you can inspect
filters, Heat Exchange Elements, power source and motors.
2. Cautions on Installing The Unit Body Upside
Down
■ Re-fit the ceiling suspension fixture in an opposite side. (If they are left as it is, the foolproof function of ceiling suspension bolts do
not work and will cause the danger of dropping of the unit.)
■ Printed indication is in a reversed position.
In particular, be careful of the arrow mark [
Electric Works
Have a specialized working contractor perform wiring in accordance with the laws and regulations of the country concerned.
■ Connect the wires shown by the broken lines.
■ Use a device for disconnection from the supply, having a contact separation of at less 3mm in all poles, which must be
incorporated in the fixed wiring in accordance with the local electrical wiring rules.
220~240V
50/60Hz
Power Source
Divide the power lines running to
the switch and the main unit.
On the product, do not attach
more than one cable to each
terminal.
Operation Switch
(1) 0 (OFF)
(2) 1 (ON)
Air Flow Switch
(3) High
(4) Low
Function Select Switch
(5) Energy Recovery
Switch
Ventilation
(To be procured
(6) Normal Ventilation
locally)
To find out the function of
each switch, refer to Page 8
of the Owner's manual.
Third main body
■ If the supply cord is damaged, it must be replaced by the manufacturer, its sevice agent or similarly qualified persons in order to
avoid a hazard.
6
450 mm or more at the place
] showing the direction of inserting a Heat Exchange Element.
Red
Supply
Capacitor
Air Fan
Orange
Yellow
Blue
Black
White
Low
High
Extra
Common
High
(LINE)
(NEUTRAL)
Power Source
Damper
Motor
Red
Exhaust
Capacitor
Air Fan
Orange
Yellow
Blue
White
Black
High
Common
Low
Extra
High
(Second main body)
Ceiling Suspension Bolt
(φ10 to φ12)
Fig. 1
Model No.
FY250ZDY2
FY350ZDY2
FY500ZDY2
Model No.
FY-250ZDY2
FY-350ZDY2
FY-500ZDY2
Model No.
2.0 μF 450VAC
FY-250ZDY2
3.0 μF 450VAC
FY-350ZDY2
3.5 μF 450VAC
FY-500ZDY2
Nut
Washer
Ceiling Suspension
Fixture
Washer
Nut
Power Source
220-240V~50Hz/
220V~60Hz
Capacitor