Remote Indicator Status LEDs
RI Status
LED State
Long Green pulse
Power-on initialisation
(no fault)
3 Green blinks
Fault
Blink Amber every 1s.
Red/Green double-blink every 14s
Un-commissioned
(or just Green when communicating).
Green/Amber double-blink every 14s
Sync
(or just Green when communicating).
Controlled by associated device; can be
Normal
set to Red ON, periodic blink Red or OFF.
Idle (low power mode)
Amber/Green double-blink every 14s
Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy
The commissioned remote indicator then synchronises with its
associated devices as the RF mesh network is created by the gateway.
(For further information on commissioning and uncommissioning, see
the Radio Programming and Commissioning Manual - ref. D200-
306-00.)
LED INDICATORS AND FAULT DESCRIPTION
The remote indicator LEDs show the status of the device as follows:
Meaning
Device is un-commissioned
(factory default)
Device is commissioned
Device has an internal trouble
Device is powered and is waiting to be
programmed.
Device is powered, programmed and
trying to find/join the RF network.
RF communications is established;
device is working properly.
Commissioned RF network is in standby;
used when the gateway is powered off.
MAINTENANCE
When changing the batteries, both should be replaced.
Identifying if a Device has been Commissioned or not
Take the device and remove all the batteries. Then insert one battery
into position #1 while watching the device LED. After a few seconds
the green LED will blink. If initially the LED gives one long green
blink, the device is un-commissioned. If however the LED gives
three short green blinks, the device is commissioned.
Patents Pending
EU Declaration of Conformity
Hereby,
Life Safety Distribution GmbH declares
equipment type
M200I-RF
The full text of the EU DoC can be requested from:
HSFREDDoC@honeywell.com
that the radio
is in compliance
with directive
2014/53/EU
I56-6235-002