Commissioning And Operation; Status Indicators; Teaching-In An Actuator; Teaching-In The First Actuator (Condition As Delivered) - SICK T4000 Serie Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6
Chapter
6

Commissioning and operation

Tab. 4: LED
indicators
162
© SICK AG • Industrial Safety Systems • Germany • Subject to change without notice • 8012206/UC32/2010-11-15
Commissioning and operation
6.1

Status indicators

The safety switch has two LEDs for status and error
messages Tab. 4 below only provides an overview; you will
find all LED signal functions in Tab. 5.
LED
Colour
STATE
Green
ERROR
Red
6.2

Teaching-in an actuator

Before the system forms a functional unit, the actuator
must be allocated to the read head using a teach-in
function.
During the "Teach-in" operation, the safety outputs and
the door signal output OUT are set to LOW, i.e. the system
is in the safe state.
6.2.1
Teaching-in the first actuator (condition as
delivered)
 Apply operating voltage to the read head; the read head
performs a self-test for approx. 10 seconds, during this
process the green LED flashes quickly (approx. 4 Hz).
The LED then flashes cyclically three times and signals
it is ready for teach-in.
 Bring the actuator near to the read head, observe a
distance of < S
process starts, the green LED flashes slowly (approx.
1 Hz) and extinguishes when the teach-in process is
complete.
 Switch off the operating voltage to the read head for at
least 3 seconds to activate in the read head the
actuator code taught-in.
Status
Meaning
Illumi-
Normal operation
nated
Flashing
see Tab. 5
Illumi-
Internal electronic fault or fault on
nated
inputs/outputs
; the approx. 60 second long teach-in