Champ® Pro LED Luminaires
PVM Series LED Fixtures
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Champ
®
PVM Series Luminaires are suitable for use in the
following areas as defined by the National Electrical Code
(NEC
).
®
Refer to the luminaire nameplate for specific maximum
ambient temperature suitability.
PVM:
NEC/CEC
• Wet location, Type 4X
UL Standards
• UL1598 Luminaires, UL1598A Marine
• UL8750
• UL50, UL50E
CSA Standards
• CSA C22.2 No. 250.0-08
WARNING
To avoid the risk of fire or electric shock, this product
should be installed, inspected and maintained by a
qualified electrician only, in accordance with all applicable
electrical codes.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during
installation and maintenance.
Luminaire must be supplied by a wiring system with an
equipment grounding conductor.
To avoid burning hands:
Make sure lens and housing are cool when performing
maintenance.
INSTALLATION
MOUNTING
1. Mount the cover module in its support position.
• Ceiling and wall mount: mark and drill desired location
on mounting surface. Secure with 1/4" (6mm) bolts or
lag screws (not provided).
• Pendant, cone, stanchion mount: securely thread onto
the appropriate NPT size conduit. Tighten set screw
located in the conduit hub. See Figure 1.
• Crouse-Hinds HTL thread lubricant must be added to
the conduit threads to prevent water from entering the
fixture.
FIGURE 1
Open
Hinge
Set-screw
Ground Wires
IF 1677 • 08/15
Copyright © 2015, Eaton's Crouse-Hinds Division
IF 1677
Luminaire construction is designed for use indoors and
outdoors in marine and wet locations, where moisture, dirt,
corrosion, vibration and rough usage may be present.
Input Voltage:
100-277 VAC 50/60 Hz
347-480 VAC 50/60 Hz
108-250 VDC 50/60 HZ
To avoid product degradation:
Make sure the supply voltage is the same as the
luminaire voltage.
Do not operate in ambient temperatures above those
indicated on the luminaire nameplate.
Use proper supply wiring as specified on the luminaire
nameplate.
All gasket seals must be clean.
Keep tightly closed when in operation.
WIRING
1.
Pull field wiring into cover module.
2.
Close all unused conduit entries with conduit
plugs provided. To prevent galling and to ensure
water-tightness, lubricate conduit plugs with
Crouse-Hinds HTL lubricant before installing, and
secure wrench-tight with at least five (5) full threads
engaged (42-52 ft.-lb. for 3/4" plugs, and 58-68 ft.-lb.
for 1" plugs).
3.
Hang LED luminaire on the cover module hinge hook.
See Figure 2a.
4.
Connect supply wires to luminaire wire leads or
terminal block per the attached wiring diagrams using
methods that comply with all applicable codes. See
Figure 2b. Tighten all electrical connections.
5.
Close driver housing
onto cover module,
making sure that all
wires are safely inside
driver housing. Tighten
captive closing screw
to 30 in.-lbs. (3.4 N-m).
Ensure two (2) bosses
on driver housing are
in contact with cover
module.
6.
Turn power on.
FIGURE 2a
DRIVER
DRIVER
(4X) SPLICE CONNECTION
LED BOARD MOUNT
CONNECTORS
INPUT
DRIVER
OUTPUT
(2X) SPLICE CONNECTION
LED BOARD MOUNT
CONNECTORS
Page 1
IF 1677 • 08/15
LINE
NEUTRAL
+ POS
L (BROWN)
INPUT
- NEG
GND
N (BLUE)
- (BLACK)
OUTPUT
+ (RED)
L
L (BROWN)
INPUT
N
N (BLUE)
G
- (BLACK)
OUTPUT
+ (RED)
+ P1 -
+ P2 -
WIRING DIAGRAM
9L/11L CONFIGURATION
5L/7L S892 REDUNDANT DRIVER CONFIGURATION
LINE
NEUTRAL
+ POS
- NEG
GND
L
L (BROWN)
N
N (BLUE)
G
- (BLACK)
+ (RED)
DRIVER COMPARTMENT
+ P1 -
GROUND
LED SUBASSEMBLY
WIRING DIAGRAM
3L/5L/7L CONFIGURATION
FIGURE 2b
Copyright © 2015, Eaton's Crouse-Hinds Division
SUPPLY WIRE
TERMINAL BLOCK
DRIVER COMPARTMENT
GROUND
LED SUBASSEMBLY
SUPPLY WIRE
TERMINAL BLOCK