Descargar Imprimir esta página

Eaton CROUSE-HINDS Champ Pro PVM Serie Manual Del Usuario página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

WIRE GUARD INSTALLATION
Loosen but DO NOT completely remove wire guard screw. If already loosened, move to next step.
Set wire guard in place by pushing it over the bottom rim of the fixture which is on the lowest casting until it sits in place
above that rim. Ensure that the wire guard is in place around the complete bottom and is not partially in place above the
rim.
Tighten the screw attached to wire guard until guard is securely attached to bottom casting. The screw will be tight
enough when the wire guard can no longer easily rotate on the fixture.
NOTE: The sheet metal tabs which the screw goes through do not need to be touching for the guard to be securely
fastened; the wire guard will be secure without those two tabs touching one another.
FIELD ASSEMBLED FIXTURES
Champ
PVM Series Lighting Fixtures, 3L-11L Watt
®
MOUNTING MODULE SERIES
PENDANT
ANGLED
CEILING
WALL
APM2
BPM2
CM2
TWM2
APM3
BPM3
CM3
TWM3
HPM2
PVM*L
MAINTENANCE
1.
Perform visual, electrical and mechanical inspections
on a regular basis. The environment and frequency
of use should determine this. However, it is
recommended that checks be made at least once
a year. We recommend an Electrical Preventive
Maintenance Program as described in the National
Fire Protection Association Bulletin NFPA No. 70B:
Recommended Practice For Electrical Equipment
Maintenance (www.nfpa.org).
2.
The lens should be cleaned periodically to ensure
continued lighting performance. To clean, wipe the
lens with a clean, damp cloth. If this is not sufficient,
use a mild soap or a liquid cleaner such as Collinite
NCF or Duco #7. Do not use an abrasive, strong
alkaline or acid cleaner. Damage may result.
3.
Visually check for undue heating evidenced by
discoloration of wires or other components, damaged
parts or leakage evidenced by water or corrosion
in the interior. Replace all worn, damaged or
malfunctioning components, and clean gasket seals
before putting the luminaire back into service.
4.
Electrically check to make sure that all connections
are clean and tight.
5.
Mechanically check that all parts are properly
assembled.
6.
If the lens is removed from the fixture, the lens
gasket must be replaced to maintain restricted
breathing ratings.
REPLACEMENT PARTS
Crouse-Hinds PVM Series Champ Luminaires are designed
to provide years of reliable lighting performance. However,
should the need for replacement parts arise, they are
available through your authorized Crouse-Hinds distributor.
Assistance may also be obtained through your local
Crouse-Hinds representative.
Crouse-Hinds Sales Service Department, 1201 Wolf Street,
Syracuse, New York 13208, Phone (866) 764-5454.
IF 1677 • 08/15
Copyright © 2015, Eaton's Crouse-Hinds Division
MOUNTING MODULE
STANCHION
NOTES:
JM5
PM5
- 2: indicates 3/4" NPT thread
- 3: indicates 1" NPT thread
- 5: indicates 1-1/2" thread
- Pendant, angled, ceiling and
stanchion mounts have one (1)
conduit entry; ceiling and wall mounts
have five (5) conduit entries
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during
installation and maintenance. Luminaire must be
supplied by a wiring system with an equipment
grounding conductor.
To avoid burning hands:
Make sure globe or refractor and lamp are cool when
performing maintenance.
INSTALLATION CHECKLIST
1.
Verify sufficient HTL lubricant is on conduit
_______
plugs (recommend approximately 1/8" bead around
the first thread of plug) and that all unused conduit
entries on the cover module are closed with
lubricated plugs.
2
._______
Verify conduit plugs are installed to at least five
(5) full threads into the cover module conduit entries.
3
Verify installed conduit plugs are torqued to
._______
42-52 ft.-lbs. for 3/4" plugs and 58-68 ft.-lbs. for 1"
plug. Making sure at least five (5) full threads are
engaged.
4.
_______
Verify supply wires are connected to luminaire
wire leads (or terminal block) per wiring diagrams.
All statements, technical information and recommendations contained herein are based on information and
tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with
Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser
should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in
connection therewith.
Page 3
5.
Verify all electrical connections are tightened.
_______
6
Verify all wires are safely and neatly inside
._______
driver housing and not on top of wire terminal. Close
driver housing onto cover module.
7.
Verify captive closing screw is tightened to 30
_______
in.-lbs. (3.4 N-m) and two (2) bosses on driver housing
are in contact with cover module.
Eaton's Crouse-Hinds Division
1201 Wolf Street, Syracuse, New York 13208 • USA
Copyright © 2015
IF 1677
Revision 4
Revised 08/15
Supersedes 06/15

Publicidad

loading