Installation manual
1
About this manual
Manual code: DCMIIN1PPFMLED
Version: 1.30
2
General Description
The FPMLED and FPMLEDPRN front-plate modules are equipped with 50 tricolour LEDs which replicate the
signals generated by the system.
The FPMLEDPRN module is equipped with an 80mm thermal printer.
This module mounts to either of the two apertures on the front of the cabinet and connects to the system via
the CAN bus cable. Each module is equipped with:
• CAN BUS cable
• 6 screws with washers for securing the module
• 1 ferrite
• Instructions manual
Figure 1 - FPMLEDPRN, page 1
[A]
LED
[B]
Thermal printer
[C]
Mounting screw locations
Connector for the CAN drive bar or
[D]
other front-plate module
[E]
Connector for front-plate module
[F]
Mini USB port
[G]
Module firmware version label
3
Mounting FPM modules to the front plate
Refer to Figure 2 - PRCAB + FPM, page 2.
The front-plate modules (FPMCPU, FPMNUL, FPMLED, FPMLEDPRN, FPMEXT) can be mounted to one of the
apertures on the cabinet front plate.
1.
Align the 6 holes on the module frame (paragraph 2 - [C]) with the 6 holes on the cabinet front-plate.
2.
Secure the module in place by fastening the supplied screws into the aligned holes.
3.
Connect the CAN BUS wire ([A] supplied):
- if the module is mounted in the upper aperture, the CAN BUS wire must be connected between the
module port ([B], paragraph 2 - [D]) and the CAN bar port ([C])
- if the module is mounted in the lower aperture and another module is mounted in the upper aperture, the
CAN BUS wire must be connected between module port ([D], paragraph 2 - [D]) and the appropriate port
on the upper module ([E], paragraph 2 - [E])
4.
Fit the ferrite ([F], supplied) to the connected CAN BUS cable.
About this manual
Technical specifications
Power supply voltage
Operating temperature
stand-by
Consumption @
27.6V
maximum
FPMLED
FPMLEDPRN
19-30 V
supplied by IFM24160 module
from -5°C to +40°C
12mA
35mA
45mA
400mA