Wiring For Single Tone Activation At Power-Up; Getting Repair Service Or Technical Assistance - Federal Signal SST3-MV Instrucciones De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Maintenance Instructions
If the contact closures are simultaneously applied to all tone
terminals, the HORN tone will override the other two tones.
If the contact closures are applied to the HORN tone and any
other tone, HORN overrides the other tone.
If the contact closures are applied to WAIL and YELP, the
WAIL tone overrides the YELP tone.

Wiring for Single Tone Activation at Power-Up

Make sure that operating power to the siren is off.
The siren can be operated by switching operating power (AC
or 24 Vdc) ON to the siren if a permanent short-wire jumper is
installed between GND and the desired tone terminal of the four-
position connector plug instead of the dry-contact closure.
Connect a 1-inch-long 22 AWG wire between GND and the
desired tone terminal of the four-position connector plug supplied
with the siren. Plug the connector into the J4 receptacle (see
Figure 1 on page 8) on the printed circuit board. Switching ON the
operating power will now activate the siren.

Getting Repair Service or Technical Assistance

Products returned for repair require a Return Authorization form
from your local distributor or from Federal Signal. To obtain
repair service or technical assistance from Federal Signal, call
708-534-4756 or 877-289-3246.
For instruction manuals and information on related products, visit:
http://www.federalsignal-indust.com.
14
Model SST3-MV Siren

Publicidad

Tabla de contenido
loading

Tabla de contenido