Configuration; Standard Settings: Ready For Use; Explanation Of Settings - Victron energy Quattro 24/5000/120-2x30-230/240V Manual

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

5. CONFIGURATION

- Settings may only be changed by a qualified electrical engineer.
- Read the instructions thoroughly before implementing changes.
- During setting of the charger, the DC fuse in the battery connections must be
removed.

5.1 Standard settings: ready for use

On delivery, the Quattro is set to standard factory values. In general, these settings are selected for single-unit operation.
Settings, therefore, do not require changing in the event of stand-alone use.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard Quattro factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on/ off
Charging characteristics
Charging current
Battery type
Discharge)
Automatic equalisation charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
Generator (AC-in-1) / shore current (AC-in-2)
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Programmable relay
PowerAssist

5.2 Explanation of settings

Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the
software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1
(priority input) or AC-in-2. Once synchronised, the output frequency will be equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1 (priority
input) or on AC-in-2. After the back feed relay has closed, output voltage will be equal to input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Inverter voltage
Output voltage of the Quattro in battery operation.
Adjustability: 210 – 245V
12
50 Hz
45 - 65 Hz
180 - 265 VAC
230 VAC
stand-alone
off
on
on
four-stage adaptive with BatterySafe mode
75% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
off
14.4 / 28.8 / 57.6 V
up to 8 hours (depending on bulk time)
13.8 / 27.6 / 55.2 V
13.2V (not adjustable)
1 hour
7 days
on
30A/16A (= adjustable current limit for PowerControl and
PowerAssist functions)
on
off
off
2
alarm function
on