MULTIMATIC 2110 2309
3110 3309
CONFIGURATION
By mean of
we can change the values and save with ENTER. Whenever we want to quit the programming sequence press
MENU. After every ENTER it will appear automatically the different screens that constitute the sequence of programming.
0
PRESSURE LINE
0,0 bar
1
LANGUAGE ENGLISH
2
SET UP MENU
3
MAX. INT. PUMP 1
OFF
4
MAX. INT. PUMP 2
OFF
MAX. INT. PUMP 3
4 bis
OFF
LEVEL PROBE
5
NO
6
PROGRAMMING MENU
START PRESSURE
7
1st PUMP
03,0 bar
STOP PRESSURE
8
1st PUMP
04,0 bar
START PRESSURE
9
2nd PUMP
10
STOP PRESSURE
2nd PUMP
9 bis
START PRESSURE
3rd PUMP
05,0 bar
10 bis
STOP PRESSURE
3rd PUMP
03,0 bar
11
START DELAY
01 s
12
STOP DELAY
01 s
CONFIGURACION
13
COMPLETED
PRESSURE LINE
0,0 bar
To start configuration sequence push MENU during 3".
By mean of keys
ENGLISH", "LANGUE FRANÇAISE", "LINGUA ITALIANA" and "IDIOMA
ESPAÑOL".
Being inside configuration menu we are acceding to the set up phase.
By mean of keys
enabling the thermal protection. This value is located over the
characteristics plate of the motor. Press ENTER for validation.
Follow the instructions of the previous step.
Only for type 3110/3309 (3 pumps)
Follow the instructions of the step 3.
If there is not an external device for the detection of the minimum water
level, press ENTER for validation. Otherwise, by mean of keys
NO by YES.
Being inside configuration menu we are having access to the phase of
programming.
This is the connection pressure for the first pump to start at the beginning of
the cycle. Due to the alternated operation sequence, it could be pump 1 or 2
for type 2110/2309 and 1,2 or 3 for type 3110/3309.
By mean of keys
Follow the instructions of the previous step. Press ENTER for validation.
Follow the instructions of point 7.
02,5 bar
Follow the instructions of point 7.
03,5 bar
Only for type 3110/3309 (3 pumps).
Follow the instructions of point 7.
Only for type 3110/3309 (3 pumps).
Follow the instructions of point 7.
This is the necessary delay to connect the pump once it has reached the
pressure of connection. By mean of keys
This timing keeps connected the pump once it has reached the
disconnection pressure. alcanzada su presión de paro. By mean of keys
choose the desired timing.
System is ready to work. Press AUTOMATIC,
green led light brights. From this moment the
display will show the working pressure.
we can choose the languages: "LANGUAGE
enter the nominal intensity value in A for pump 1
choose the desired pressure values.
choose the desired timing.
EN
MENU
MENU
3"
ENTER
ENTER
ENTER
ENTER
ENTER
change
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
AUTOMATIC
7