MECHANICAL MONITOR ATTACHMENT
The Monitor is to be mounted on the waterway with eight
minimum of six threads engagement. The front of the monitor in Figure 2 is considered to be point 4 and is above the identification
tag. The bolts must be tightened in a criss cross pattern progressively increasing tightening torque to a maximum of 100 foot
pound dry.
NOTE: Not recommended to mount on a raised flange or have a butterfly valve between the flanges.
This may cause damage to the monitor's flange when tightening the bolts.
THE ROTATIONAL AND ELEVATION STOPS SET THE BOUNDARIES FOR THE AREA IN WHICH THE MONITOR IS ALLOWED TO TRAVEL
AND MEETS THE REQUIREMENTS OF THE NFPA. The upper row controls the right travel, and the lower row controls the left travel.
The angles for the rotational stops are with respect to the "reference direction" illustrated in Figure 2. The monitor is shipped with
the upper row stop at point 3 which stops the monitor at 90° right, clockwise and the lower row stop at point 5 which stops the
monitor at 90° left, counterclockwise. All other positions are achieved by switching the factory set stops and the plugs in the desired
stop location . Both the stops and the plugs have a
the desired right, clockwise or left, counterclockwise rotation . The elevation stop sets the upper and lower limits of the elevation . The
monitor is shipped with the upper limit at 45° or 90° above horizontal (mounted vertically) and the lower limit at 45° below horizontal
to meet NFPA. All other vertical positions are achieved by switching plugs and stops to the desired locations as indicated in Figure 4.
MECHANICAL ATTACHMENT OF CONTROLLER AND LOGIC BOX
A . CONTROLLER AND TETHER CONNECTOR ATTACHMENT
Pump panel cut out and mounting hole dimensions are given in Figure 3. The controller and tether connector should be installed
in the pump panel prior to electrical connection to the logic box .
B. LOGIC BOX ATTACHMENT
The StreamMaster logic box must be mounted close enough to the monitor to allow the 8 ft . monitor wiring harness sufficient
slack to allow the monitor to travel through its full range . The logic box overall dimensions and mounting hole dimensions are
given in Figure 5 .
WARNING: Do not extend the monitor wiring harness.

ELECTRICAL INSTALLATION INSTRUCTIONS

A. CONTROLLER, JOYSTICK OR TETHER CONNECTOR ELECTRICAL ATTACHMENT
These instructions are for attaching the controller, joystick or the tether connector to the logic box. The controller, joystick and
tether connector are supplied with 8 ft . of cable .
STEP 1 If the control box includes an attached cable skip to STEP 6.
STEP 2 Determine the length of #20-7 cable needed, add 10 inches, then cut. For example, if a five foot length of cable
is needed, add 10 inches and cut the cable 5 foot 10 inches long .
STEP 3 Remove the cable grip nut and washer from the control box and put it on the cable with the threads facing the box . On
the same end of the cable remove 4 inches of the outer casing of the cable and strip back
the 7 wires .
STEP 4 Take the 7 ring terminals from the plastic bag and crimp them on the 7 wires . Remove the four control box cover screws
and set the control box cover aside . Thread the 7 wires through the cable grip attached to the control box and attach
them to the proper terminals . Tighten the cable grip nut and washer on the cable to
the cable grip on the control box to secure the cable . Reattach control box cover and
secure with the four screws
5
/
inch bolts and nuts of grade five minimum and suitable washers with a
8
/
inch hex head . Refer to Figure 2 to determine which stop location is needed for
1
2
3
3
/
inch from each of
8
STRAIGHT
RIGHT
RAISE
WHITE
WHT
WHT
FOG
LEFT
LOWER

Publicidad