LOCK ACTIVATION, MAGNETIC LOCK OR INDUCTIVE LOAD
CARES
In cases of inductive load activation, as locks or magnetic lock, turnstile's bobbins or
collector turnstile, besides others, to avoid the return of electric current during the bobbins
shutdown, use the indicated components according the instructions below.
DIODE FILTER CONNECTION SCHEME (level 1 protection - Applies to direct current "DC")
SOLENOID
CAPACITOR (level 1 protection - Applies to alternate current "AC")
SOLENOID
DIODE + CAPACITOR (level 2 protection - Applies to direct current "DC")
DIODE
SOLENOID
LINE FILTER FOR LOCKS
(level 3 protection - Applies to direct or alternate current. Filters and rectifies the "AC" current to "DC")
SOLENOID
Solenoid power
CATHODE
DIODE
OR
ANODE
Solenoid power
SUPPRESSOR CAPACITOR "X2 0,1uF 275V
CATHODE
OR
ANODE
Solenoid power
SUPPRESSOR CAPACITOR "X2 0,1uF 275V
LINE FILTER FOR LOCKS
Solenoid power
- NOTE: THERE IS NO POLARITY