LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified ) Location
IS,Class I, Division 1, Group A,B,C,D T4..T6
Ex ia IIC T4..T6 Ga
Class I, Zone 0, AEx ia IIC T4..T6 Ga
Terminal: 41,42,43
51,52,53
Connect to passive or
non-energy storing
devices such as RTD's
Resistors and
Thermocouples only.
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
Canadian Electrical Code (CEC).
Channel 1 and Channel 2 are separate channels and therefore separate shielded cables
shall be used for each channel.
Substitution of components may impair intrinsic safety.
Revision date:
2014-10-20
18
CSA Installation drawing 6333QC01
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
43
13
+
42
11
-
41
CH1
23
+
53
21
52
-
51
CH2
6333B1B
Version Revision
V1R0
6333V104-ES
WWW.PRELECTRONICS.COM
Non Hazardous Location
Barrier
Barrier
Terminal:
11, 13 and
21, 23
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10μH
Ci: 6.2nF
Co(Ca) > ∑(Ci+Ccable)
Lo(La) > ∑ (Li+Lcable)
Page: