Compressor: relay SPST 20(8) A, 250Vac
Fans: relay SPST 8(3) A, 250Vac
Defrost: relay SPDT 8(3) A, 250Vac
Other output: buzzer (optional)
Serial output: TTL standard
Communication protocol: ModBUS – RTU
Data storing: on the non-volatile memory (EEPROM)
Kind of action: 1B
Pollution grade: 2
Software class: A
Rated impulsive voltage: 2500V
Over voltage Category: II
Operating temperature: 0 to 60°C (32 to 140°F)
Storage temperature: -30 to 85°C
Relative humidity: 20 to 85% (no condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-40 to 230°F)
PTC probe: -50 to 150°C (-58 to 302°F)
Resolution: 0.1°C or 1°C or 1 °F (selectable)
Accuracy (ambient temp. 25°C): ±0.7 °C ±1 digit
15. CONNECTIONS
15.1 XW30L - CL01
15.2 XW60LS - CL02
TTL

16. DEFAULT SETTING VALUES

Label
Name
Set Set point
Hy Differential
LS Minimum set point
US Maximum set point
Ot Thermostat probe calibration
P2P Evaporator probe presence
OE Evaporator probe calibration
odS Outputs delay at start up
AC Anti-short cycle delay
CCt Continuous cycle duration
CCS Set point for continuous cycle
COn Compressor ON time with faulty probe
COF Compressor OFF time with faulty probe
CF Temperature measurement unit
rES Resolution
Lod Probe displayed
dLy Display temperature delay
tdF Defrost type
dtE Defrost termination temperature
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dSd Start defrost delay
dFd Displaying during defrost
dAd MAX display delay after defrost
Fdt Draining time
dPo First defrost after start-up
dAF Defrost delay after fast freezing
Fnc Fan operating mode
Fnd Fan delay after defrost
Fno Fan delay after compressor start
Fct Differential of temperature for forced
activation of fans
1598029000 XW30L-XW60LS CLD IT-GB-FR-SP-TD r2.1 23.09.2015
Range
°C/°F
LS to US
-5.0
0.1 to 25.5°C
2.0
1 to 255°F
-50°C to SET
-30.0
-58°F to SET
SET to 110°C
20.0
SET to 230°F
-12 to 12°C
0
-21 to 21°F
n=not present; Y=pres.
y
-12 to 12°C
0
-21 to 21°F
0 to 255 min
0
0 to 50 min
1
0.0 to 24h00min
0.0
-55.0 to 150.0°C
-5.0
-67 to 302°F
0 to 255 min
15
0 to 255 min
30
°C; °F
°C
in=integer; dE= dec.point
dE
P1; P2
P1
0.0 to 20min00sec, res. 10 sec
0
EL=el. heater; in= hot gas
EL
-50 to 50°C
8.0
1 to 120 hours
6
0 to 255 min
30
0 to 99 min
0
rt, it, SEt, DEF
it
0 to 255 min
30
0 to 120 min
0
n=after IdF; y=immed.
n
0.0 to 23h50min, res. 10 min
0
C-n, o-n, C-y, o-Y
c-n
0 to 255min
10
0 to 255min
1
0 to 50°C
10
Label
FSt Fan stop temperature
Fon Fan on time with compressor off
FoF Fan off time with compressor off
FSU Fan operating mode
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
ALd Temperature alarm delay
dAO Delay of temperature alarm at start up
i1P Digital input polarity (13-14)
i1F Digital input 1 configuration (13-14)
did Digital input alarm delay (13-14)
Nps Number of activation of pressure switch
odc Compress and fan status when open door
rrd Regulation restart with door open alarm
HES Differential for Energy Saving
LoC Keyboard lock enabling
Adr Serial address
PbC Kind of probe
dP1 Room probe display
dP2 Evaporator probe display
rSE Real set
rEL Software release
Ptb Map code
Level
- - -
Pr1
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr1
Pr1
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
Pr2
XW30L – XW60LS
Name
Range
-50 to 50°C
-58 to 122°F
0 to 15 min
0 to 15 min
Std, Fon, FOF
rE= related to set;
Ab = absolute
SET to 110.0°C
SET to 230°F
-50.0°C to SET
-58°F to SET
0 to 255 min
0 to 23h50min, res. 10 min
oP=opening;CL=closing
EAL, bAL, PAL, dor;
dEF; Htr, AUS
0 to 255 min
0 to 15
no; Fan; CPr; F_C
n; Y
-30 to 30°C
-54 to 54°F
n; Y
1 to 247
PtC; ntC
--
--
actual set
--
--
°C/°F
Level
2,0
Pr2
0
Pr2
0
Pr2
FoF
Pr2
rE
Pr2
10
Pr2
10
Pr2
10
Pr2
2.0
Pr2
cL
Pr2
EAL
Pr2
0
Pr2
15
Pr2
no
Pr2
y
Pr2
0
Pr2
n
Pr2
1
Pr2
ntC
Pr2
-
Pr2
-
Pr2
-
Pr2
1.8
Pr2
-
Pr2
8/20