USER PROGRAMMING
When the system is operating, one of fi ve displays
may beshown. Pressing NEXT will alternate between
the displays. One of the displays is always the
current time of day. The second display is one of
the following: days remaining or volume
remaining. Days remaining is the number of
days left before the system goes through a
regeneration cycle. Capacity remaining
is the cubic meters that will be treated before
the system goes through a regeneration cycle.
The third display shows the current treated water
fl ow rate through the system. If 1.0 is selected
in Step 2CS, an "A" in front of the fl ow rate indicates that the
tank with the control valve on it is in service. If "b" is displayed,
the tank with the in/out head is in service. The fourth display
will show either dP or hold if the dP switch is closed. The fi fth
display shows the kg of salt remaining or fl ashes "SALT" fi ll
when the calculated kg of salt falls below a safety level. The fi fth
display will not appear if the valve is a WS2, set up as a
fi lter or if the Set Low Salt Warning is set to off (see last
step in OEM Softener System Setup). The user can
scroll between the displays as desired.
If the system has called for a regeneration that will
occur at the preset time of regeneration, the words
REGEN TODAY will appear on the display.
If a water meter is installed, the word "Softening" or "Filtering"
fl ashes on the display when water is being treated (i.e. water is
fl owing through the system).
In Alternator Systems when a unit is waiting to initiate the first cycle step of
regeneration, "REGEN PndG" is displayed.
"STbY" is displayed in Alternator Systems when a valve is in Standby state.
"REGEN PndG FILL RINSE" is displayed whenever a zero-capacity tank has transferred to
an off-line state and is currently waiting to initiate the second portion of a regeneration
cycle. Viewed only when Delayed Rinse and Fill is set to ON.
REGEN TODAY will
Flash if a regeneration
is expected "Tonight."
26