WPL44/ WPL44NP   MasterCool® Mirage Window Evaporative Cooler 
Trouble Shooting Chart 
PROBLEM 
Unit will not start 
Insufficient Cooling 
Water in air stream 
High indoor humidity  
Odor in home 
Rapid mineral buildup 
on media pads 
 
 
 
 
 
 
 
 
 
 
 
PROBABLE CAUSE 
a. No Power  
 
b. Tripped Circuit Breaker 
c. Blown Fuse 
d. Electrical fault 
a.  Inadequate water distribution 
     (pads not saturated) 
 
 
b. Pads dirty or covered with 
     mineral deposits 
a. Water system has leaks or 
     loose connections 
 
b. Water is not being absorbed 
     by media pads, and entering 
     straight into airflow  
a. Insufficient air flow 
b. Unsatisfactory exhaust  
a. Bacterial growth in reservoir  
 
 
b. Air intake is picking up 
    ambient odor from 
    surroundings 
a. Hard water  
SOLUTION 
a. Verify unit plugged in; 
    and outlet is functional 
b. Reset Circuit Breaker 
c. Replace fuse 
d. Call Champion Help line 
a. Check water distribution tray and 
    hose for blockages.  
‐   Verify pump operating correctly 
‐   Check water supply for correct flow 
b. Wash dirt & deposits off pads 
    or replace pads  
a. Check all water connections, tubing, 
    distribution tray for loose fittings, 
    leakage or tears. 
b. Check condition of pads. Clean or 
    replace as necessary . 
a. Increase fan speed 
b. Open doors or windows more 
a. Clean unit regularly with 
    disinfectant or add a liquid 
    bacteriostat into the water  tank  
b. Remove source of odor or move  
    cooler to another window  
a. Increase maintenance cycle and 
    wash off scale more often. Check  
    orifices are clear of mineral buildup.  
 