Operating Instructions
Evaluation Units CMS-E-BR

Electrical connection

Warning! In case of an error, loss of the safety
function through incorrect connection.
The auxiliary contact 23/24 must not be used as
a safety output.
Lay the connection cables with protection to
prevent the risk of short circuits.
Caution! Risk of damage to equipment or malfunc-
tions as a result of incorrect connection.
All the electrical connections must either be
isolated from the mains supply by a safety trans-
former according to EN 61558-2-6 with limited
output voltage in the event of a fault, or by other
equivalent isolation measures.
For use and operation as per the
ments, a power supply with the feature "for use
in class 2 circuits" must be used. The same
requirement applies to the safety outputs. Alter-
native solutions must comply with the following
requirements:
a) Electrically isolated power supply unit with a
max. open-circuit voltage of 30 V/DC and a limited
current of max. 8 A.
b) Electrically isolated power supply unit in combi-
nation with fuse as per UL 248. This fuse should be
designed for max. 3.3 A and should be integrated
into the 30 V/DC voltage section.
The devices are tested in accordance with UL 508
and are intended for rail mounting in the control
cabinet.
They are not tested as safety components in the
context of the UL definition (e.g. for potentially
explosive atmospheres).
All electrical outputs must have an adequate
protective circuit for inductive loads. The outputs
must be protected with a free-wheeling diode for
this purpose.
The tightening torque for the screws on the connec-
tion terminals must be 0.5 ... 0.6 Nm.
If no read heads are connected to the plug-in ter-
minals provided in the evaluation units, the jumpers
supplied must be inserted in accordance with the
wiring diagram.
Safety in case of faults
Terminals A1 and A2 for connection of the power
supply and all outputs (safety and auxiliary contact)
are reverse polarity protected.
Setup
If the evaluation unit does not appear to function
when operating voltage is applied (green UB LED
does not illuminate), the unit must be returned
unopened to the manufacturer.
Check whether the safety contact is switched by
opening and closing the safety door.

LED indicators

The LEDs S1 and S2 indicate whether actuator and
require-
read head are correctly aligned in relation to each
other. The status of the safety contact cannot be
seen from the LEDs.
Function
Operating voltage
Contacts 23/24 and 13/14 open
Contacts 23/24 and 13/14 closed
Read head x (x = 1...4)
Actuator in the operating distance
NC contact in the read head open
f
NO contact in the read head closed
f
Actuator not in the operating distance
NC contact in the read head closed
f
NO contact in the read head open
f
If the green and red LEDs light up simultaneously
f
(e.g. D11 and D22), the related actuator is not
fully in the operating distance.
If the actuators for all the connected read heads
f
are in the operating distance (or 2-pin jumpers have
been fitted in the evaluation unit), safety contact
13/14 and auxiliary contact 23/24 are activated
(the green OUT LED illuminates).
In the evaluation unit the green LEDs are wired in
f
series in the following sequence: D11 - D21 - D31
- D41. This means that the green LED (e.g. D41)
can illuminate only if the upstream LEDs D11/D21/
D31 are also illuminated.
If the actuation speed falls below the minimum
f
speed, contacts 13/14 and 23/24 remain open.
Service and inspection
No servicing is required. Regular inspection of
the following is necessary to ensure trouble-free
long-term operation:
correct switching function
f
secure mounting of components
f
loose connections.
f
In the event of damage or wear and tear, the dam-
aged system component must be replaced.
If the safety door is not frequently used, the system
must be subjected to a regular function test as part
of the inspection schedule.

EC declaration of conformity

The manufacturer named below herewith declares
that the product fulfills the provisions of the direc-
tive(s) listed below and that the related standards
have been applied.
EUCHNER GmbH + Co. KG
LED
Color
State
Kohlhammerstraße 16
U
green
ON
B
70771 Leinfelden-Echterdingen, Germany
OUT
red
ON
OUT
green
OFF
Directives applied:
OUT
red
OFF
Machinery directive 2006/42/EC
f
OUT
green
ON
EMC directive 2014/30/EU
f
RoHS directive 2011/65/EU
f
Dx1
green
ON
Standards applied:
Dx2
red
OFF
EN ISO 13849-1:2015
f
Dx1
green
OFF
EN 14119:2013
f
EN 50178:1997
Dx2
red
ON
f
EN 60947-5-1:2004/A1:2009
f
EN 60947-5-2:2007/A1:2012
f
EN 60947-5-3:2013
f
EN 61000-6-3:2007/A1:2011
f
The original EC declaration of conformity can also
be found at: www.euchner.com