Terminator
The following installation procedures are suggested guidelines
for the installation of the Terminator ZT-P-WP Kit.
Kit Contents . . .
1
2
PN 27656
3
Item
Quantity
Expediter Assembly
Support Cap with O-Ring
1
1
Threaded Grommet Compressor
Grommet
Support Base with O-Ring
2
1
Junction Box Lid
3
1
Junction Box Base with O-Ring and M25 Dust Cap
4
1
Nut
5
1
Banding
Thermostat w/ Terminal Blocks
(Refer to terminal specifi cations for maximum allowable wire size)
Thermostat Type
6
1
ZT-C-100
ZT-C-200
ZT-C-300
ZT-C-500
7
1
Capillary Armouring w/ Glands
8
1
Junction Box Cord
9
1
Blind Plug
10
1
Bracket
11
3
Screws
12
3
Washers
Order Separately . . .
PETK Power and End Termination Kits (per cable)
PETK-1
for RSX, VSX, BSX
PETK-2
for KSX, HTSX
PETK-3-ZT for HPT, FP
2
1
7
6
Item
Quantity
1
1
RTV Tube
2
1
Power Connection Boot
3
2
Conductor Wire Pins
4
1
Braid Wire Pin
5
1
Ground Sleeve
6
1
End Cap
7
1
Tape Strip (PETK-3-ZT only)
8
1
Grommet (PETK-3-ZT only)
9
1
End Termination Caution Label
ZT-P-WP
TM
4
5
6
7
8
10
9
Description
Control Range
0°C to +100°C
0°C to +200°C
0°C to +300°C
20°C to +500°C
3
4
5
8
9
Description
INSTALLATION PROCEDURES
Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper
type and quantity has been received.
4. Store in a dry location.
Order Separately . . .
IEK Insulation Entry Kit (per cable)
11
IEK-SXL:
for RSX, VSX,
IEK-SXM
for BSX
12
IEK-SXS
for KSX, HTSX
IEK-HPT
for HPT, FP
Dimensions . . .
155mm
200mm
Warnings
. . .
• Due to the risk of electrical shock, arcing and fi re caused
by product damage or improper usage, installation or
maintenance, a ground-fault protection device is required.
• Installation must comply with Thermon requirements
(including form PN 50207U for Ex systems) and be installed
in accordance with the regulations as per the norm EN IEC
60079-14 for hazardous areas (where applicable), or any
other applicable national and local codes.
• Component approvals and performance ratings are based
on the use of Thermon specifi ed parts only.
• De-energize all power sources before opening enclosure.
• Avoid electrostatic charge. Clean only with a damp cloth.
• Keep ends of heating cable and kit components dry before
and during installation.
• Minimum bending radius of heating cable is 32 mm (except
HPT is 57 mm and FP is 19 mm).
• Individuals installing these products are responsible for
complying with all applicable safety and health guidelines.
Proper Personal Protective Equipment (PPE) should be
utilized during installation. Contact Thermon if you have any
additional questions.
Tools Required . . .
Certifi cations/Approvals . . .
IP66 -60°C Ta +50°C T5, 100°C; -60°C Ta +40°C T6, 85°C
Ordinary & Hazardous Locations
FMG 10.0022X Ex db eb IIC T5-T6, Ex tb IIIC T100°C-T85°C
1725
II 2 GD Ex db eb IIC T5-T6, Ex tb IIIC T100°C-T85°C FM10ATEX0058X
Terminator has additional hazardous area approvals including:
• GGTN • Kazakhstan
2
205mm
190mm
50mm
3 mm
8 mm
Terminator-LN-Tool
(order separately)
28 mm
33 mm