7. UPS Operation
Step 5
Rotate switch to "UPS" (S3M100KX model), or Turn OFF the Q4 Maintenance Bypass breaker (S3M120KX, S3M160KX and
S3M200KX models).
S3M100KX (100 kVA)
Step 6
Secure the mechanical locking plate to the switch (S3M100KX model) or Q4 Maintenance Bypass breaker (S3M120KX,
S3M160KX and S3M200KX models).
S3M100KX (100 kVA)
Step 7
Press Power ON/OFF button for 2 seconds until a beep is heard, then release to start the inverter.
The critical load is now supported in Line Mode.
Step 8
ON
OFF
Q4
Maintenance Bypass
S3M120KX (120 kVA)
Q4
Maintenance Bypass
S3M120KX (120 kVA)
60
OFF
ON
Q4
Maintenance Bypass
S3M160KX/S3M200KX
(160 kVA/200 kVA)
Q4
Maintenance Bypass
S3M160KX/S3M200KX
(160 kVA/200 kVA)