5 - PROGRAMMABLE FUNCTIONS
Example: blocked Comfort minimum temperature setting for the
Summer mode (
)
cooling
Mode
OK
Mode
OK
Note: any previously blocked settings
are cancelled by setting
5.4 - TEMPERATURE ADJUSTMENT METHODS
The thermostat is factory set to work in
ON OFF
(adjustable from 0.2 °C to 1.2 °C).
The hysteresis value must be set according to the system's thermal
inertia; a low value is recommended for systems with radiators made of
e.g. cast iron and a high value for systems with fan coils.
Set the blocked value of the
maximum temperature
via
the
or
button.
As opposed to the differential, the temperature can be adjusted
PROPORTIONALLY PROP
(default 10 minutes)
This system maintains the desired temperature more stable, whilst
Press
OK
to save and
increasing the user's comfort sensation and saving on energy
move on to the subsequent
consumption.
setting or keep the button
Setting example: WINTER mode
pressed for at least 4 sec to
T Set = 20 °C - Cycle = 10 minutes
save the new setting and
t = 20,5 °C
exit the programming
t = 20,4 °C Device is 1 min ON - 9 min OFF
menu.
t = 20,3 °C Device is 2 min ON - 8 min OFF
t = 20,2 °C Device is 3 min ON - 7 min OFF
t = 20,1 °C Device is 4 min ON - 6 min OFF
t = 20,0 °C Device is 5 min ON - 5 min OFF
t = 19,9 °C Device is 6 min ON - 4 min OFF
t = 19,8 °C Device is 7 min ON - 3 min OFF
t = 19,7 °C Device is 8 min ON - 2 min OFF
t = 19,6 °C Device is 9 min ON - 1 min OFF
t = 19,5 °C Device always on
A long cycle is recommended for systems with high thermal inertia (cast
iron radiators, floor systems) and a short cycle for systems with low
thermal inertia (fan coils).
/
with a preset differential value (
°C
Adjustable differential from
0.2 °C to 1.2 °C
On
Off
On
Time
Load
(
) setting cycles from 7 to 20 minutes
Device is always off
DIFFERENTIAL MODE
Hysteresis
) of
0,5 °C
EN
°C
Device
20,8
OFF
20,6
20,4
20,2
20,0
19,8
19,6
Device
ON
19,4
19,2
0
2
4
6
8
10
Minutes
Select the desired mode
33