Technical Parameters; Temperature Sensor - Elko EP TEV-2 Manual De Instrucciones

Ocultar thumbs Ver también para TEV-2:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 17

Technical parameters

Function:
Supply terminals:
Supply voltage:
Input:
Max. dissipated power
(Un + terminals):
Tolerance of supply voltage:
Measured circuit
Measuring terminals:
Temperature ranges:
-20 to 20 °C / -4 to 68 °F
Hysteresis (sensitivity):
Sensor:
Faulty sensor indication:
Accuracy
Accuracy of settings (mech.):
Dependance on temperature:
Output
Number of contacts:
Rated current:
Switching output:
Peak current:
Switched voltage:
Output indication:
Mechanical life:
Electrical life:
Other information
Operation temperature:
Operation position:
Protection degree:
Overvoltage cathegory:
Pollution level:
2
Max. cable size (mm
):
Dimensions:
Weight:
Standards:
EN 60255-1, EN 60255-26, EN 60255-27, IEC 60730-2-9

Temperature sensor

-40°C to 125°C (-40°F to 257°F)
Range:
Scanning element:
Tolerance:
In air/ in water:
In air/ in water:
Cable material:
Terminal material:
Protection degree:
Electrical strength:
Insulation resistance:
Length:
Weight:
τ65 (95): time, which sensor needs to heat up on 65 (95) % of ambient temperature of
environment, in which is located.
Resistive values of sensors in dependance on temperature
Temperature (°C / °F)
20 / 68
30 / 86
40 / 104
50 / 122
60 / 140
70 / 158
Tolerance of sensor NTC 12 kΩ is ± 5% by 25 °C / 77 °F.
TEV-2
TEV-3
one-level thermostat
L - N
230 V AC / 50 - 60 Hz
max. 2.5 VA / 0.5 W
3 W
±15 %
T - T
5 to 35 °C / 41 to 95 °F
3 °C (± 1.5 °C) / 37.4 °F (± 2.7 °F)
thermistor NTC 12 kΩ
red LED fl ashing
5 %
< 0.1 % / °C
1x changeover / SPDT (AgNi / Silver Alloy)
16 A / AC1
4000 VA / AC1; 384 W / DC
30 A / < 3 s
250 V AC
red LED
7
3x10
0.7x10
5
-30 to +50 °C (-22 to 122°F)
any
IP65 assembly
III.
2
solid wire 2.5 / with sleeve 1.5 (AWG 12)
110 x 135 x 66 mm (4.33˝x 5.3˝x 2.6˝)
270 g (9.5 oz.)
274 g (9.7 oz.)
TZ-0
TC-0
-20 °C to 80 °C (-4 °F to 176 °F)
NTC 12K
NTC 12K
±(0.15°C + 0.002|t|)
±(0.15°C + 0.002|t|)
(τ65) 62 s / 8 s
(τ0.5)
(τ95) 216 s / 23 s
(τ0.9)
PVC unshielded,
PVC
2x 0.25 mm
stainless steel
polyamid
IP67
IP67
2500 VAC
2500 VAC
> 200 MΩ at 500 VDC
> 200 MΩ at 500 VDC
110 mm (4.3")
100 mm (3.9")
4.5 g (0.16 oz.)
5 g (0.17 oz)
Sensor NTC (kΩ)
14.7
9.8
6.6
4.6
3.2
2.3
Function
red LED
green LED
TEV-2 and TEV-3 are universal single thermostats for universal use. In case ambient
temperature is higher than set temperature relay is open (function HEATING), for cooling
function (opposite function) is possible to use NC contact of relay (V2).
Warning
The device is constructed to be connected into 1-phase main and must be installed in
accordance with regulations and norms applicable in a particular country. Installation,
connection and setting can be done only by a person with an adequate electro-technical
qualifi cation which has read and understood this instruction manual and product func-
tions. The device contains protections against over-voltage peaks and disturbing elements
in the supply main. Too ensure correct function of these protection elements it is neces-
sary to front-end other protective elements of higher degree (A, B, C) and screening of
disturbances of switched devices (contactors, motors, inductive load etc.) as it is stated in
a standard. Before you start with installation, make sure that the device is not energized
and that the main switch is OFF. Do not install the device to the sources of excessive elec-
tromagnetic disturbances. By correct installation, ensure good air circulation so the maxi-
mal allowed operational temperature is not exceeded in case of permanent operation and
higher ambient temperature. While installing the device use screwdriver width approx.
2 mm. Keep in mind that this device is fully electronic while installing. Correct function of
the device is also depended on transportation, storing and handling. In case you notice
any signs of damage, deformation, malfunction or missing piece, do not install this device
and claim it at the seller. After operational life treat the product as electronic waste.
DECLARATION OF CONFORMITY
ELKO EP declares that the TEV-2 / TEV-3 type of equipment complies with Directives 2014/30/EU, 2011/65/EU,
2015/863/EU and 2014/35/EU. The full EU Declaration of Conformity is available at:
www.elkoep.com/thermostat-tev-2
www.elkoep.com/thermostat-tev-3
≤ 18 s
≤ 48 s
2
2 / 2
hysteresis
V1
sensor
failure

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tev-3

Tabla de contenido