Configuration - AKO -522044 Manual Del Usario

Alarma de detección de gases refrigerantes + alarma de hombre encerrado
Ocultar thumbs Ver también para AKO-522044:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Configuration

Auto-configuration function
This function configures the station automatically according to the devices connected in each input.
When the station receives power for the first time (factory settings), it will sequentially turn on all the
input indicators, which indicates that it has not been configured.
Press the auto-configuration button for more than 5 seconds to activate this function (see page 14),
and the station will emit 5 short beeps and turn on the four input indicators for a few seconds.
Return to factory settings
Press auto-configuration button 5 times (See page 14), and the station will emit a confirmation beep
and return to the factory setting.
IMPORTANT: Both functions should be carried out during the first 5 minutes after connecting the power
supply.
Pre-alarm jumper (gas detectors)
It allows activating pre-alarm detection. (See page 17). Before using this option, make sure that regulations allow
for only two alarm levels.
MODBUS address selector
It allows configuring the station's MODBUS address (See page 17), and then this address can be reassigned using
the management programme. If this unit is connected in a network, make sure you use a free address.
Self-diagnosis function
The unit incorporates a self-diagnosis system for the gas detector and wiring between the detector/button and the
alarm station, and if the wiring malfunctions, the station will emit 3 beeps every 2 minutes and the corresponding
input indicator will turn on. In the event of an operating error in the gas detector, its LEDs will turn on alternately.
Detector heating time
After receiving the electrical power supply, the gas detector needs a heating time of around 5 minutes,
during which it will NOT detect leaks. This time is indicated by means of a quick flashing of the green led
on the detector itself.
5.- Operation
Alarm station
* Input indicators with connected gas detectors will stay on indicating that they are disabled. The rest of the inputs
STATUS
3
4
With power supply
Without power
supply/With battery
Without power
supply/Without
will turn on in the event of an alarm (active button).
1
2
3
4
According to
ON
active alarms
Flashing
ON*
OFF
OFF
ALARM STATION
RELAYS
Gas Alarma
Trapped person
According to active
According to active
alarms
According to active
1
2
3
4
1
2
3
4
5
18
1
OBSERVATIONS
-
alarms
Disabled gas
alarms
detectors
-
6
7
2
3
4

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ako-522104Ako-52214

Tabla de contenido