Descargar Imprimir esta página

Bosch FCS-320-TP1 Guia De Instalacion página 26

Ocultar thumbs Ver también para FCS-320-TP1:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 29
26
en
1.
2.
3.
4.
5.
6.
Connecting the FCS-320-TP/-TT series
See Figure 4, Page 5:
Terminal Terminal block X6 Function
1
2
3
4
5
6
7
8
9
F.01U.130.927 | 2.0 | 2010.12
First, clearly mark the fixing points on the installation position provided on the
equipment. Use the supplied drilling jig as an aid. To guarantee a firm, low-vibration hold,
the unit must be secured with four screws (max. 6 mm ∅ (0.4 inches) for wall mounting,
max. 4 mm ∅ (0.2 inches) for MT-1 unit mounting).
Using four screws appropriate for the installation method, attach the unit securely to the
surface or to the unit mounting. Ensure that the unit is not fixed under mechanical stress
and that the screws are not tightened too tightly, otherwise damage or undesirable
resonance noises could occur.
To balance out unevenness and/or prevent vibrations, vibration absorbers (subject to
separate order) must be used.
Using a screwdriver, carefully punch out the required cable entries on the housing (max.
5 x M20 and 2 x M25).
Fit the cable entry/entries as required with M20 or M25 connections (2 x M25 and 1 x
M20 included in the delivery) by pushing them into the cable entry/entries.
Route the connection cable(s) (max. 2.5 mm
connections and into the unit. Cut them to the required length inside the unit.
Wire the unit according to the connection information described below.
Al 1
+ Ext. Displ.1
- Ext. Displ.1
+ Reset
- Reset
+ 24V
- 24V
FCS-320-TP1 | FCS-320-TP2 | FCS-320-TT1 | FCS-320-TT2
2
) through the prepared M20 or M25
NO contact for 1st alarm relay
C contact for 1st alarm relay
NC contact for 1st alarm relay
Remote indicator for 1st detector module
+24 V reset input
0 V reset input
+24 V power supply
0 V power supply
Bosch Sicherheitssysteme GmbH

Publicidad

loading

Este manual también es adecuado para:

Fcs-320-tp2Fcs-320-tt1Fcs-320-tt2