28
en
1.
2.
3.
4.
Troubleshooting Using Flash Codes
Malfunctions and unit statuses are indicated via the flash codes of the detector module LEDs:
Flash code of detector module LEDs
1 flash
2 x flashes
3 x flashes
4 x flashes
Permanently lit Hardware defect in the detector module
LED flash code on the motherboard (LED1/LED2)
1 flash
2 flashes
3 flashes
4 flashes
5 flashes
6 flashes
7 flashes
8 flashes
Technical data
Power supply
Rated supply voltage
Max. current consumption (at 24 V)
-
-
-
-
-
-
Reset board current consumption
Max. wire gauge
Housing material
Housing color
Protection category according to EN 60529
Permissible temperature range
-
-
-
Permissible relative humidity (non-condensing)
Sound power level
Life cycle of the fan (12 V)
F.01U.130.927 | 2.0 | 2010.12
Check the system after installation using the FAS-ASD-DIAG Diagnostic Software.
The unit must be operated for at least 30 min prior to the airflow being initialized to bring
it up to operating temperature.
To initialize the connected pipe system, press the S2 flow-init button (see Figure 5,
Page 5) on the detector module concerned until the green operating LED on the unit
starts to flash. Initialization is complete after approx. 10 seconds. Following successful
initialization, the operating LED lights up permanently.
No further modifications may be made to the pipe system during or after initialization.
The unit's fan voltage must also remain unchanged following initialization. Otherwise, the
initialization procedure must be repeated.
Airflow initialization (flow-init) active
Airflow too small (obstruction)
Airflow too great (break)
Unit upload (approx. 2 minutes)
Error: internal voltage monitoring 1
Error: internal voltage monitoring 2
Error: fan voltage monitoring
Error: air pressure correction voltage monitoring
Software error
Internal error 1
Internal error 2
Unit upload (approx. 2 min)
Starting current 6.9 V (without reset board)
Starting current 9 V (without reset board)
In standby, fan voltage 6.9 V (without reset board)
In standby, fan voltage 9 V (without reset board)
On alarm, fan voltage 6.9 V (without reset board)
On alarm, fan voltage 9 V (without reset board)
FCS-320 series Aspirating Smoke Detector
PVC pipe system
ABS pipe system
FCS-320-TP1 | FCS-320-TP2 | FCS-320-TT1 | FCS-320-TT2
14 V DC to 30 V DC
24 V DC
FCS-320
-TP1/-TT1
300/300 mA 320/330 mA
300/300 mA 320/330 mA
200/200 mA 220/230 mA
275/260 mA 295/310 mA
210/230 mA 240/290 mA
285/290 mA 315/370 mA
Max. 20 mA
2.5 mm
Plastic (ABS)
Papyrus white, RAL 9018
IP 20
-20 °C to +60 °C
-10 °C to +60 °C
-40 °C to +80 °C
10 to 95%
45 dB(A)
43,500 hrs at 24 °C
Bosch Sicherheitssysteme GmbH
FCS-320
-TP2/-TT2
2