Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

8 Technical features

COnsTrUCTiOn sPeCifiCATiOns
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
electrical input specifications
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Number of input phases
Waveform on output
With battery operation
Type of operation
electrical specifications on output
Rated output voltage
Active output capacity on nominal load
Apparent output capacity on nominal load
Overload capacity
Number of phases on output
Daker DK 4.5, 6, 10 kVA
3 100 53
52 Kg
440 x 176 x 680
Electronic protection against overloading
and short-circuiting. Shutdown on
reaching operating limit and overheating.
Automatic shutdown due to protection
triggering
from 0 to +40 °C
from 20 to 80% non-condensing
IP21
< 50 dBA
230 V
from 160 V to 280 V
50 or 60 Hz ± 5Hz
25 Arms
Single phase
sinusoidal
on line - double conversion
230 V ± 2%
4050W
4.5KVA
105% continuous
120% for 30 seconds
140% for 10 seconds
Single phase
3 100 54
52 Kg
440 x 176 x 680
33 Arms
5.4KW
6KVA
43

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Daker dk 6 kvaDaker dk 10 kva