START UP
► Open the main tap (A).
5.2

Draining the product

1
1
Heat pump circuit air
bleed valve
► Open the air bleed valve (1) while fi lling the heat pump
circuit.
► Open the air bleed valve (2) while fi lling the heating
circuit with water.
► Close the vent as soon as water fl ows (repeat the
operation several times if necessary).
Caution!
b
Risk of damage in case of bad
purge!
If air purging is not done properly,
this may cause damage to the
appliance.
Make sure the system is properly
purged air.
22
2
2
Heating circuit air bleed
valve
5.3

Installing the casing

1
1
Front casing
► Put the front casing back on.
5.4
Available pump pressure head for heat
pump circuit
B
A
A
Installation heating
circuit fl ow
A
800
700
600
500
400
300
200
1
100
0
500
1000
1500 2000 2500 3000
A
Pressure (mbar)
B
Flow rate (l/hour)
1
Position "III"
B
Installation heating
circuit fl ow
3
2
2
Position "II"
3
Position "I"
0020166669_04 - 03/15 - Vaillant