TROUBLESHOOTING

Fault signal
Road tanker does not
provide approval.

RESTORATION

If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is
no dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.

MAINTENANCE

Upon proper ASSEMBLY and OPERATION, the product is maintenance-free.
cover due to contaminated operating media.
Proper operation is no longer provided for.
Remove the limit indicator from the tank!
Perform a visual inspection  sensor must be free!
Carefully clean the inside of the sensor cover with a brush and a cleaning
agent.
Install the limit indicator into the tank and repeat CONTROL.

FUNCTION CHECK

DISPOSAL

In order to protect the environment, products contaminated with water-
hazardous substances or that have come in contact with such substances must
not be disposed of in the domestic waste, to public waters or channels.
The product must be disposed of via local collection stations or a recycling station.

TECHNICAL DATA

Ambient temperature

WARRANTY

We guarantee that the product will function as intended and will not leak during
the legally specified period. The warranty term begins when the product is
handed over to the customer. The scope of our warranty is based on Section 8
of our terms and conditions of delivery and payment.
Part No. 15 382 57 a
Action
 Check connector.
 Check cable or replace the limit indicator.
 MAINTAIN the sensor.
Malfunctions and contamination of the sensor in the sensor
-25°C to +50°C
Limit indicator GWG - type GWD -issue 2
Upon electrical installation and within the
framework of the repetitive inspections, the
function of the GWG must be checked and
documented using a precision instrument. An
annual function check is recommended; this
check can be performed while filling the
tank/battery tank in combination with GWG and
the overfill prevention mechanism on the road
tanker. See OPERATION! If the shut-down time
determined during the function check is ≥ 1.5s,
the GWG must be replaced immediately.
11 / 12