INSTALLATION GUIDE.

6.1 INSTALLATION PREPARATION.

Before installation check possible lose or damage of the device during transportation and read
the complete user manual.
Prepare a suitable environment for installation
Install the device.
Connect the signal cables.

6.2 ENVIRONMENT ENQUIRIES.

It is recommended to take into account the following point related with the installation
environment:
 When installing multi-row of racks, please make the distance 1.2~1.5M between front
door and back door, and the distance 0.8M between rack and wall.
 The floor of the room where is installed the device should be non-conducting, dust free.
Anti-static material volume resistivity: 1x10
resistance: 1MΩ, floor bearing weight: > 450Kg/m
Working temperature: for long term operation: 5 ÷ 40º C, for short term operation: 0 ÷ 45º.
Relative humidity: for long term operation: 20% ÷80 %, for short term operation: 10% ÷ 90%.

6.3 GROUNDING REQUIREMENTS.

Good ground wire design is the base of the whole system, and is essential to lightning protection and
anti-interference. The system must follow above principles:
Keep good electrical contact between both ends of outer conductor and shielding layer and the
appearance of metal case of the connected device.
Make sure that connections of both ends of the ground wire are with good electrical contact
and prepare for corrosion prevention treatment.
Do not use other device for ground wire electrical connection.
The sectional area of ground wire from rack connecting to anti-thunder unit must be greater
than or equal to 25mm
2
7
10
÷ 1x10
Ω, ground current-limiting
2
.
8