Passive Infrared Vacancy Sensors RMS100, RMS120 and
Passive Infrared Occupancy Sensors RMS101, RMS121
Pre-installation Checklist
1. Check rating of sensor to make sure it is suitable for the application. RMS100, RMS120 sensors are
to be used with 120VAC, 60 Hz, 25Watts minimum, 500Watts maximum incandescent load ONLY.
2. Do not install sensor if the product or lens has any visible damage.
3. If moisture condensation is evident, allow product to dry before installing.
Installation Procedure
1. DISCONNECT POWER.
2. Make sure sensor's OFF/AUTO switch is in the OFF (down) position (see Figure 1).
3. Mount sensor 42 to 54 inches (107 to 137 cm) above floor
(remove old wall switch, if applicable).
4. Connect GREEN wire to equipment grounding conductor
"GND" (green, green/yellow or bare wire).
5. Connect BLACK wire to "HOT" or "LINE" wire (see Figure 2).
6. Connect the other BLACK wire to lighting "LOAD" wire (see Figure 2).
7. Mount device in box and secure wall plate.
8. Restore power.
9. Move sensor's OFF switch to ON position.
10. Installation complete. AT sensor starts with 15 minute time
out (Factory default). To further verify correct installation with
shortened time delay or use other settings, see below:
Front Press Switch (FPS) Basic Operation (See Additional
Functions Below).
1. Occupancy Sensor: When lights pressed off, they stay off
with motion with a 30 minute time out from the last detected
motion; after the 30 minute time out, unit returns to auto mode.
2. Vacancy Sensor: When lights pressed off, they stay off until
the FPS is pressed again.
3. When lights pressed on they stay on with motion until the
unit times out.
To Shorten Time Delay To 30 Seconds (For Test Only).
1. Remove door (gently pull the FPS push-button from face of occupancy sensor).
2. Note the Time adjust setting, then set time adjust to minimum (full counterclockwise position).
3. Step out of field of view of sensor (LED stops flashing) for more than 30 seconds.
4. Reenter field of view of sensor, LED will flash and the lights will come on.
5. Exit test by resetting the time adjust to the prior position or at factory default (12 o'clock position).
Range: 30 seconds to 30 minutes.
6. Place door back on sensor.
Occupancy Sensor Only:
Daylight Control Lighting (Holds lights off if sufficient natural light is available).
1. Make sure the desired natural light level (without lights on) is present.
2. Press and hold Front Press Switch for 5 seconds (LED flashes 2 times), step away from sensor.
3. During setting, LED flashes and sensor reads the light level in the room for 30 seconds.
4. At the end of this period, the sensor stops flashing and the daylight light level will be set.
NOTE: If desired, reset to factory default settings by pressing and holding front press switch 10 seconds
(LED flashes 3 times). Disables daylight control.
INSTALLATION INSTRUCTIONS
Fig.1 – View Behind Door
Fig. 2 – Wiring Diagram
Line
LIGHT
Neutral
Load
Ground
BLACK
BLACK
GREEN