5.2 Switching on the 30 Hz filter (INP A, INP B)
5.3 Input mode
* where bounce occurs, e.g. with contacts
MN05401004E
The filter provides input
damping*
30 Hz filter off (f max )
30 Hz filter on
Count input and count
direction input
INP A: Count input
INP B: Count direction input
Differential input
IINP A: count input adding
INP B: count input
subtracting
Totalizing
INP A: count input adding
INP B: count input adding
Quadrature input
INP A: count input 0°
INP B: count input 90°
Quadrature input with pulse
doubling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A
will be counted
Quadrature input with pulse
quadrupling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A
and INP B will be counted.
For the frequency
measurement, INP C may
be operated independently
of the counter input modes.
5.4 Multiplying factor (counter)
5.5 Dividing factor (counter)
5.6 Decimal point (counter)
5.7 RESET mode (counter)
It can be set from 00.0001
up to 99.9999.
"0" is not accepted!
It can be set from 00.0001
up to 99.9999.
"0" is not accepted!
The decimal point defines
the way of displaying the
count values. It does not
affect counting.
0
no decimal place
0.0 one decimal place
0.00 two decimal places
0.000 three decimal places
manual reset via the red
RESET key
no reset (red RESET key
locked)
3