Technical data
General specifications
Signal type
Programming
Supply
Connection
Rated voltage
Power consumption
Input
Connection
Rated values
Open circuit voltage/short-circuit current
Switching point/switching hysteresis
Line fault detection
Control input
Pulse duration
Output
Connection
Relay
Contact loading
Minimum switch current
Energized/De-energized delay
Mechanical life
Trip value
Transfer characteristics
Accuracy
Start-up override
Frequency range
Rotation direction detection
Electrical isolation
Input/Output
Input/power supply
Output/power supply
Output/Output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU
Low voltage
Directive 2014/35/EU
Conformity
Electromagnetic compatibility
Degree of protection
Input
Ambient conditions
Ambient temperature
Mechanical specifications
Degree of protection
Mass
Dimensions
Mounting
Data for application in connection
with hazardous areas
EC-Type Examination Certificate
Group, category, type of protection
Input
Voltage
Current
Power
Supply
Maximum safe voltage
Output
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
Digital Input
via DIP switch and programmable
Power Rail or terminals 14+, 15-
U
20 ... 30 V DC
n
≤ 1.5 W
Input I: terminals 1+, 2+, 3- ;
Input II: terminals 4+, 5+, 6-
acc. to EN 60947-5-6 (NAMUR)
approx. 8 V DC / approx. 8 mA
1.2 ... 2.1 mA / approx. 0.2 mA
breakage I ≤ 0.1 mA , short-circuit I > 6 mA
sensor power supply approx. 8.2 V, impedance 1.2 kΩ
> 200 µs for standstill monitoring,
> 250 µs for rotation direction detecion
output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
2 changeover contacts
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
2 mA / 24 V DC
approx. 20 ms / approx. 20 ms
7
10
switching cycles
f
for standstill monitoring:
max
0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz
adjustable via DIP switch (S1 and S2)
5 % (S3 = I), 30 % (S3 = II)
5 seconds or 20 seconds, programmable
≤ 2 kHz
90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
EN 61326-1:2013 (industrial locations)
EN 61010-1:2010
NE 21:2006
IEC 60529:2001
EN 60947-5-6:2000
-20 ... 60 °C (-4 ... 140 °F)
IP20
approx. 150 g
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
on 35 mm DIN mounting rail acc. to EN 60715:2001
PTB 00 ATEX 2080
¬ II (1)G [Ex ia Ga] IIC
¬ II (1)D [Ex ia Da] IIIC
¬ I (M1) [Ex ia Ma] I
Ex ia
U
10.5 V
o
I
13 mA
o
P
34 mW (linear characteristic)
o
U
253 V AC / 125 V DC (Attention! U
m
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
is no rated voltage.)
m
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
KFD2-SR2-Ex2.W.SM
eff
eff
eff
eff