Wiring the input terminals
The device can be connected to a three−phase system (TN, TT or IT system acc. to VDE 0100
T 300/IEC 364−3) with a rated voltage area AC 400 V ... AC 500 V (see the following
illustrations).
Alternatively, the device input can also be connected to a DC−bus system with a voltage
range DC 450 V ... DC 800 V,
(see section "24 V supply from DC−bus connection".
)
Note!
In case of a phase failure a permanent operation with rated power is ensured.
TN-S
3/N/PE AC 400 ... 500 V
45 ... 65 Hz
L1
L2
L3
N
PE
5
L1 L2 L3
PE
TT
3/N AC 400 ... 500 V
3/N AC 400 ... 500 V
45 ... 65 Hz
45 ... 65 Hz
L1
L1
L2
L2
L3
L3
N N
5
L1
L1
L2
L2
L3
L3
PE
PE
5
Circuit−breaker 6 A/ 10 A/ 16 A (characteristic B or C)
EDKZV1200 DE/EN/FR/ES/IT 1.0
TN-C
3/PEN AC 400 ... 500 V
45 ... 65 Hz
L1
L2
L3
PEN
5
L1
L2 L3
L3
PE
IT
3 AC 400 ... 500 V
45 ... 65 Hz
L1
L2
L3
5
L1
L2
L3
PE
l
Electrical installation
Wiring the input terminals
2
ezvxx00−001_06
21