Setting and using method
n Function table for the selection of 'OPER_SW' and the input
signal
CN_MODE input
OPER_SW
FAN
0
0
0
0
2,3,6,7,A,B,E,F
1
1
1
1
Others
-
CN_WIND input
OPER_SW
Low
0
0
0
0
8,9,A,B,C,D,E,F
1
1
1
1
Others
-
CN_OPER
OPER_SW
Thermal
0
0
4,5,6,7,C,D,E,F
1
1
Others
-
Notes
1) Thermal On : This input will change automatically desired temperature
Desired Temperature 18 °C In cooling mode
Desired Temperature 30 °C In heating mode
No function In FAN mode
12 Dry contact for thermostat
OPER_SW
Function
HEAT
COOL
0
0
NA
0
1
COOL
1
0
HEAT
1
1
NA
0
0
FAN
0
1
NA
1
0
NA
1
1
NA
-
-
NA
Function
Middle
High
0
0
NA
0
1
High
1
0
Middle
1
1
NA
0
0
Low
0
1
NA
1
0
NA
1
1
NA
-
-
NA
Function
Operation
0
Thermal Off + Stop
1
Thermal Off + Run
0
Thermal On + Stop
1
Thermal On + Run
-
NA

Setting of 'TEMP_SW'

n When setting the desired temperature of the Dry contact
Module
: When operating the indoor unit using Dry contact module's desired temperature, set the desired
temperature according to the 'TEMP_SW' setting.
If Thermostat priority control mode is disabled, the desired temperature can be reset by other controller
- Use the 'TEMP_SW' to set the temperature as shown below.
Setting and using method
Not use Dry Contact
TEMP.
18
19
20
21
module's Desired
(°C)
temp. function
'TEMP SW'
0
1
2
3
4
setting
TEMP.
23
24
25
26
27
28
29
(°C)
'TEMP SW'
6
7
8
9
A
B
C
setting
*. E, F : Reserved
Installation manual 13
22
5
30
D