Vive Integral Fixture Controls
Part of the Vive System
041600
Please read before installing
Rev. B
04/2018
DFCSJ-OEM-OCC Vive Integral Fixture Control with Sensor
DFCSJ-OEM-RF Vive Integral Fixture Control (RF only)
9.5 – 20.5 V-
IEC SELV / NECR Class 2
UL2043 Plenum Rated
250 mA max
Vive Integral Fixture Controls
Controls up to 4 drivers (IEC 60929 Annex E.2 requires each driver to limit the sink/
source current draw to 2.0 mA maximum). See wiring diagrams for more details.
Important Notes:
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 131 °F (0 °C and 55 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
• Sensor should be mounted to fixture in orientation that makes it parallel to
the floor when fixture is installed in ceiling.
• Clean only with soft, damp cloth, no chemical cleaners.
• DO NOT paint.
• Intended for installation in fixture manufacturer's facility only.
Default Functionality
Fixture Controls
Auto On level: DFCSJ-OEM-OCC only
(not applicable for DFCSJ-OEM-RF)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period: 15 minutes
For more information, see
www.lutron.com/TechnicalDocumentLibrary/3691039.pdf
www.lutron.com/TechnicalDocumentLibrary/048642.pdf
www.lutron.com/TechnicalDocumentLibrary/ApNote106.pdf
*
For set-up, programming, and
troubleshooting with a Vive system,
please refer to the installation
instructions included with the Vive hub
or at www.lutron.com
FCC information and IC information
This device complies with part 15 of the FCC Rules and Industry Canada
license-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause interference, and (2) this
device must accept any interference, including interference that may
cause undesired operation. Modifications not expressly approved by
Lutron Electronics Co., Inc. could void the user's authority to operate this
equipment.
NOTE: This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on,
the user is encouraged to try to correct the interference by one or more
of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• C onnect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each fixture, you will need:
One Fixture Control
PIR lens
LED/Daylight sensor lens
Button
OR
Vive Integral Fixture Control (RF only)
Vive Integral Fixture Control with Sensor
(DFCSJ-OEM-RF)
(DFCSJ-OEM-OCC)
Note: Neither Daylighting functionality nor occupancy
sensing is available in the DFCSJ-OEM-RF
Start Here
Review the Vive Integral Fixture Controls App Note (048642) at www.lutron.com for Wiring
and Fixture Construction Guidelines.
1. Connect Wires using Diagrams Below
• V ive Integral Fixture control contains two 18 AWG (0.75 mm
2
), solid copper wires.
Fixture Control
120 – 277 V~
digital link interface
Vive Integral Fixture Controls with
EcoSystem or DALI Driver*
Driver
Maximum Number
per Fixture Control
EcoSystem driver
4
* P lease see the Notes section for additional details
SR+/DALI+
Driver with self-powered DALI link
SR-/DALI-
120 – 277 V~
Fixture Control with Driver with
Self-powered DALI Link
Driver
Maximum Number per
Fixture Control
PhilipsR SR driver
2
OsramR DEXALT
3
driver
2. Install Integral Fixture Control
• E nsure knockout and adjacent surfaces are free from burrs, oil, chemicals, debris, etc.
• D o not push on the PIR lens or button to install the Fixture Control. Push on the center of the Fixture Control.
• P ush firmly on the Fixture Control around the entire perimeter until it sits flush against the intended fixture mounting surface.
A special tool from Lutron can be provided to facilitate installation.
• D o not fully enclose within the metal fixture.
Customer Assistance | 1.844.LUTRON1 USA, Canada, and the Caribbean | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com
At least one EcoSystem driver + Fixture Control digital link interface (DFC-OEM-DBI)
EcoSystem driver
LED lens
Button
+
OR
At least one driver with self-powered DALI link
(see 3691039 or 048642 on www.lutron.com for list)
Driver with self-powered DALI link
S+
S-
Vive Integral
Fixture Control
E1
E2
EcoSystem driver
120 – 277 V~
E1
E2
EcoSystem driver
120 – 277 V~
Vive Integral
Fixture Control
For applications that require more drivers than shown here,
contact the driver manufacturer.
Note: When using multiple drivers with self-powered DALI link, SR+/
DEXAL+ from the drivers must be tied together and the SR-/DEXAL-
from the drivers must be tied together. Do NOT mix "+" and "-" when
using multiple drivers."
+
Fixture Control
digital link interface
3. Fixture Control Self-Test (REQUIRED)
The Vive integral fixture control supports a self-test mode in order to verify proper RF communication after
being installed in a fixture. In case of self-test failure, the fixture must not be released to customers until the
wiring and/or fixture construction is adjusted to improve RF performance until the fixture passes the self-test.
See Wiring Best Practices section on the Vive Integral Fixture Controls App Note (048642) at
www.lutron.com for details.
Until one or more of the following conditions are met, the fixture control automatically enters self-test on
power-up:
• The fixture control has previously been powered continuously for more than 60 minutes.
• The fixture control is associated to any other devices or a Vive system.
Resetting the fixture control to factory defaults will reset the above conditions and re-enable automatic
self-test entry.
The Fixture Control Self-Test is conducted as follows:
1. W hile the test is in progress, the status LED alternates between green and red. During the test, the Vive
integral fixture control will not respond to button presses or commands from other Lutron
Clear Connect devices.
2. Fixture will turn ON to full intensity for 5 seconds and then will turn OFF for 5 seconds.
3. Once the self-test is complete:
a. I f the fixture passes, the status LED blinks green twice, repeating every 2 seconds, and the fixture will
turn ON.
b. I f the fixture fails, the status LED blinks red twice, repeating every 2 seconds, and the fixture will
remain OFF.
4. To exit the self-test mode after completion, press the button or wait 5 minutes to exit automatically.
Note: Do NOT disconnect power to the fixture until the pass/fail determination has been made.
4. Basic Functionality End-of-Line Test
1. Provide power to the fixture.
2. Fixture will go to the driver's previous light level.
3. P ress the button to toggle the load state. Light will fade to ON (or OFF) over 1 second. Green LED
will stay lit for 2 seconds after releasing the button.
4. T oggle the load again (if necessary) to ensure the lights are on. This will make sure the lights turn ON when
power is applied the next time (at job site).
5. Remove power.
Notes:
1. E- and E+ from the DFC-OEM-DBI can go to either the E1 or E2 terminal on the EcoSystem driver.
2. S- and S+ from the DFC-OEM-DBI can go to either wire from the Vive Integral Fixture Control.

Publicidad

loading

Resumen de contenidos para Lutron DFCSJ-OEM-OCC

  • Página 1 Required Components Customer Assistance | 1.844.LUTRON1 USA, Canada, and the Caribbean | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com Vive Integral Fixture Controls For each fixture, you will need: At least one EcoSystem driver + Fixture Control digital link interface (DFC-OEM-DBI)
  • Página 2: Troubleshooting

    Customer Assistance | 1.844.LUTRON1 USA, Canada, and the Caribbean | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com Vive Integral Fixture Controls Programming with a Vive Hub Part of the Vive System Note: For further information U se an iOSR or AndroidT D ownload the Lutron O pen the app and follow ALL PROGRAMMING IS OPTIONAL on set up, programming, and compatible device.
  • Página 3: Commandes De Luminaires Intégrales Vive

    Composants requis Commandes de luminaires Assistance à la clientèle | 1.844.LUTRON1 États-Unis, Canada et les Caraïbes | +1.888.235.2910 Mexique | +1.610.282.3800 Autres | www.lutron.com Pour chaque luminaire, vous aurez besoin de : intégrales Vive Une commande de luminaire Au moins un pilote EcoSystem + interface de liaison numérique de la commande de luminaires (DFC-OEM-DBI) Lentille PIR Appartient au système Vive...
  • Página 4: Restaurer Les Réglages D'uSine

    Commandes de luminaires Assistance à la clientèle | 1.844.LUTRON1 États-Unis, Canada et les Caraïbes | +1.888.235.2910 Mexique | +1.610.282.3800 Autres | www.lutron.com intégrales Vive Programmation avec un hub Vive Appartient au système Vive Remarque : Pour plus U tilisez un appareil compatible avec iOSR T éléchargez l’application O uvrez l’application et suivez TOUTE PROGRAMMATION EST OPTIONNELLE d’information sur la configuration,...
  • Página 5: Controles Integrales De Artefactos Vive

    Componentes requeridos Controles integrales Asistencia al cliente | 1.844.LUTRON1 E.U.A., Canadá y el Caribe | +1.888.235.2910 20.7702.0657 México | +1.610.282.3800 Los demás | www.lutron.com Para cada artefacto, se necesitará: de artefactos Vive Al menos un controlador EcoSystem + interfaz de enlace digital de control de artefactos (DFC-OEM-DBI)
  • Página 6: Solución De Problemas

    Controles integrales Asistencia al cliente | 1.844.LUTRON1 E.U.A., Canadá y el Caribe | +1.888.235.2910 20.7702.0657 México | +1.610.282.3800 Los demás | www.lutron.com de artefactos Vive Programación con un hub Vive Parte del sistema Vive Nota: Para obtener información adicional U tilice un dispositivo compatible con D escargue la aplicación Abra la aplicación y siga TODA LA PROGRAMACIÓN ES OPCIONAL sobre la configuración, programación y iOSR o AndroidT.

Este manual también es adecuado para:

Dfcsj-oem-rf