Right Terminal
Description
Used for the connection of the internal speaker (8Ω 30W).
Speaker
BUS
Not used in Stand-Alone configuration.
GRN / YEL
AUX RED/ COM
Input DC power terminals.
BLACK
The maximum current drain from these terminals is 200mA.
connect the wires according to the indicated colors.
LED
This terminal is for triggering LED2:- LED2 activates when LED Terminal is connected
to COM (0V).
(Status LED2)
LAMP Input
Connect LAMP Terminal to COM (0v) to turn Cover Illumination ON (if fitted).
In BUS mode, lamp input works as defined in the control panel. Note: Connection of
LAMP Terminal to COM over-rides BUS Control, LAMP will be ON if LAMP Terminal is
connected to COM.
Optional 13.8 VDC,
1.6A
Tamper Output
(0.1A, 24V N.C)
Anti Approach Output
(0.1A, 24V N.C)
Trouble Output
70 mA max
Trigger (C+ or C-)
Strobe Input
BUS Mode
The following explains the various wiring and connection procedures that must be performed when wiring
the sounder:
Left Terminal
Description
PS +
Use these terminals to connect an alternative power supply 13.8VDC 1.6A to the
sounder.
PS-
NOTES:
The maximum current that the sounder can draw from these terminals is 1.6A
compared to 200 mA from the AUX RED and COM BLK terminals.
When a power supply is connected to these terminals there is no need to connect a
power supply to the AUX RED and COM BLK terminals.
Right Terminal
Description
Used for the connection of the internal speaker (8Ω 30W).
Speaker
BUS YEL/ BUS
Connect these terminals in BUS mode configuration, point to point according to the
indicated colors
GRN
To
Tamper
Battery
ON
CTS
DIP1
1 2 3 4
5
CTS
ON
DIP2
CONFIG
LED2
1 2 3 4
5
Figure 1: Stand Alone Wiring
To Lamp
Power
LED1
Strobe
In BUS configuration,
To Internal
Speaker
13.8VDC ,
200 mA (max)
Status LED2
Lamp Input
ON/Off
7