CURRENT MEASUREMENT CHARACTERISTICS
Characteristics with the 714P.200 clamp
Display range
Measurement range
Resolution
Intrinsic error (zero corrected)
Frequency operating range
Zero correction in DC
Beyond 200A DC, the display indicates «-OL» or «+OL» according to the polarity of the current
measured.
Beyond 200A peak (AC), the display indicates "OL".
Specific characteristics in MIN/MAX mode:
Extreme capture time: about 100 ms, displayed every 400 ms.
Specific characteristics in PEAK mode:
Intrinsic error: 10% L + 5 pt.
Capture time for the PEAK value: 1 to 4 ms according to the peak value.
Measuring current with a 1mV/A clamp
Refer to the description of measurement with the 714P.200 clamp, except there is no
indication of clamp presence.
Characteristics with a 1MV/A clamp
The following table indicates the tester's accuracy alone, while considering that the
clamp connected to the tester has a transfer ratio of 1 mV/A for direct reading. For
total measurement error, add to the tester's error that of the clamp used.
Display range
Measurement domain
Resolution
Intrinsic error (corrected zero)
(tester alone)
Input impedance
Frequency operating range
Correcion du Zéro en DC
18
40,00 A
0,02-39,99 A DC
0,15-39,99 A AC
10 mA
2% L + 2 pt
10 to 5000 Hz
Up to ± 6 A
400,0 A
0,2 - 399,9 A DC
0,5 - 399,9 A AC
100 mA
300 kΩ
400,0 A
40,00-170,0 A
170,0-200,0 A
peak or DC
peak or DC
100 mA
4000 A
400 - 1400 A
peak or DC
1 A
1%L +2 pt
Up to ± 30 A
5% L